Functions
Alarms and Alarm Configuration
2.12
Alarms and Alarm Configuration
EDS500 devices have an alarm concept to communicate certain error conditions with an
alarm relay, LEDs for display or software signalisation. The individual alarms (referring to
interfaces or the system) are summarised in the system-wide alarm state. The alarms have
three levels of severity.
Alarm level
Description
Alarm- Relais
state
System
alarm LED
(Alarm)
Subsystem Alarm
LED (DSL Alarm,
FO Alarm)
No alarm: off
No alarm /
information
There are no or only informative
conditions
Normal
Off
Information: on
Warning
Pre alarm: there is a noncritical
error
Normal
Flashing
On
Alarm
Alarm: there is a critical error
Alarm
On
On
Table 14:
Alarm level and signalling
The alarm relais is described in EDS500 Manual - Part 1: Alarm-Relais (X2).
The LED display is described in EDS500 Manual - Part 1: Display Elements.
The alarm table can be displayed via the command line interface (CLI) ant the Web interface.
The alarm table can also be evaluated with SNMP (refer to Chapter 2.27.3, "Vendor Specific
Device MIB" and Chapter 2.27.4, "Trap Server and Traps").
Alarm
Stage
Enabled
(as
default
value)
Config-
urable
Reason
Command
Speed mis-
match
Warning
Yes
Yes
Negotiated data rate
does not match set
data rate.
<set switch {fo1
| fo2} [no] {warn-
duplex-mismatch
| warn-speed-mis-
match}>
Link down
Alarm
No
Yes
Shows that the link is
interrupted.
<set switch fo1
alarm-ifdown>
Link up
Alarm
No
Yes
Shows that the link is
established.
<set switch fo1
alarm-if-up>
Overtemper-
ature
Alarm
Yes
Yes
The allowed system
temperature has been
exceeded.
<set system
overtemp-warning
{40-125}>
System
booting
Alarm
Yes
No
The system starts
anew.
Duplex mis-
match
Warning
Yes
Yes
Settings for duplex of
the communication
partners do not match
(shared links?)
<set switch {fo1
| fo2} [no] {warn-
duplex-mismatch
| warn-speed-mis-
match}>
Link aggre-
gation mis-
match
Alarm
Yes
No
Settings for chan-
nel bundling do not
match as one of the
Table 15:
Alarms
1KGT151021