ACH550-UH User’s Manual
101
Group 32: Supervision
This group defines supervision for up to three signals from Group 01, Operating Data. Supervision
monitors a specified parameter and energizes a relay output if the parameter passes a defined limit.
Use Group 14, Relay Outputs, to define the relay and whether the relay activates when the signal is too
low or too high.
Group 32: Supervision
Code Description Range
Resolution
Default
S
3201
SUPERV 1 PARAM
101…199
1
103
Selects the first supervised parameter.
• Must be a parameter number from Group 01 Operating Data.
• If the supervised parameter passes a limit, a relay output is energized.
• The supervision limits are defined in this group.
• The relay outputs are defined in Group 14 Relay Outputs (definition also specifies which supervision limit is
monitored).
LO
≤
HI
Operating data supervision using relay outputs, when
LO
≤
HI.
• Case A = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
OVER
or
SUPRV
2
OVER
. Use for monitoring when/if the supervised signal
exceeds a given limit. The relay remains active until the
supervised value drops below the low limit.
• Case B = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
UNDER
or
SUPRV
2
UNDER
. Use for monitoring when/if the supervised signal
falls below a given limit. The relay remains active until the
supervised value rises above the high limit.
Note!
Case LO
≤
HI represents a normal hysteresis.
LO
>
HI
Operating data supervision using relay outputs, when
LO>HI.
The lowest limit (
HI
3203) is active initially, and remains
active until the supervised parameter goes above the
highest limit (
LO
3202), making that limit the active limit.
That limit remains active until the supervised parameter
goes below the lowest limit (
HI
3203), making that limit
active.
• Case A = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
OVER
or
SUPRV
2
OVER
. Initially the relay is de-energized. It is energized
whenever the supervised parameter goes above the
active limit.
• Case B = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
UNDER
or
SUPRV
2
UNDER
. Initially the relay is energized. It is de-energized
whenever the supervised parameter goes below the
active limit.
Note!
Case LO>HI represents a special hysteresis with two separate supervision limits.
3202
SUPERV 1 LIM LO
Depends on selection
-
60.0 Hz
Sets the low limit for the first supervised parameter. See 3201
SUPERV
1
PARAM
above.
3203
SUPERV 1 LIM HI
Depends on selection
-
60.0 Hz
Sets the high limit for the first supervised parameter. See 3201
SUPERV
1
PARAM
above.
3204
SUPERV 2 PARAM
101…199
1
104
Selects the second supervised parameter. See 3201
SUPERV
1
PARAM
above.
Value of supervised parameter
Case A
0
Energized (1)
0
HI
(3203)
t
t
t
LO
(3202)
Case B
Energized (1)
LO
(3202)
t
HI
(3203)
Value of Supervised Parameter
Case A
0
Energized (1)
0
t
t
Case B
Energized (1)
Active Limit