1MRS240173-IB B
Section 5
4x Registers
REF615R
47
DPU2000R Modbus Point List Mitigation Manual
5.3.2
Operation records
REF615R substitutes Modbus events for the operation records in DPU2000R
41435
KVab/ KVan (Mag)
100
41435
100
LD0.FLTMSTA1.VoltsAB.mag.f
KVab in per unit
41453
100
LD0.FLTMSTA1.VoltsA.mag.f
KVan in per unit
41436
KVbc / KVbn (Mag)
100
41436
100
LD0.FLTMSTA1.VoltsBC.mag.f
KVbc in per unit
41454
100
LD0.FLTMSTA1.VoltsB.mag.f
KVbn in per unit
41437
KVca / KVcn (Mag)
100
41437
100
LD0.FLTMSTA1.VoltsCA.mag.f
KVca in per unit
41455
100
LD0.FLTMSTA1.VoltsC.mag.f
KVcn in per unit
41438
Vab / Van (Ang)
1
N/A in REF615R
41439
Vbc / Vbn (Ang)
1
N/A in REF615R
41440
Vca / Vcn (Ang)
1
N/A in REF615R
41441
Pos Seq KV (Mag)
100
41441
100
LD0.FLTMSTA1.VPsSeq.mag.f
in per unit
41442
Neg Seq KV (Mag)
100
41442
100
LD0.FLTMSTA1.VNgSeq.mag.f
in per unit
41443
Pos Seq V (Ang)
1
N/A in REF615R
41444
Neg Seq V (Ang)
1
N/A in REF615R
41445
Fault Location
10
41445
LD0.FLTMSTA1.FltDisKm.mag.f
Distance to fault measured in
pu
41446-41447
fault impedance,
real
1000
41446-
41448
1000
LD0.FLTMSTA1.FltZ.cVal.mag.f
41446-41447 mapped for
impedance magnitude, 41448
mapped for angle.
41448-41449
breaker operate
time
1000
41449-
41450
1000
LD0.FLTMSTA1.OpTm.mag.f
41450-41451
Relay operate time
1000
N/A in REF615R
41452
Record status
41452
Record status
DPU2000R
register addr.
DPU 2000R
description
Scale
REF615R
register
addr.
Scale
IEC 61850 path
Comments on REF615R
Modbus points mapping
REF615R Modbus protocol only reads the fault records generated after the
device powers up.WebHMI can be used to read entire set of fault records
saved in the relay.
To find out the entire set of fault records in REF615R, please check
"Feeder Protection and Control REF615R Modbus Point List Manual" with
Document ID: 1MRS240052-IB.
REF615R Modbus server only provides Modbus events generated after the
device powers up. WebHMI or ftp tool can be used to upload a complete
set of event records stored in the flash memory.
Содержание DPU2000R
Страница 1: ...B Relion Protection and Control REF615R DPU2000R Modbus Point List Mitigation Manual ...
Страница 2: ......
Страница 12: ...Section 1MRS240173 IB B 6 REF615R DPU2000R Modbus Point List Mitigation Manual ...
Страница 56: ...Section 5 1MRS240173 IB B 4x Registers 50 REF615R DPU2000R Modbus Point List Mitigation Manual ...
Страница 58: ...Section 6 1MRS240173 IB B 6x Registers 52 REF615R DPU2000R Modbus Point List Mitigation Manual ...
Страница 65: ......