Section-5
04-3006_S5_OPM_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc
Page 12/14 ABB
Modifications reserved
5.2.3
Replacement of a Module in Capacity Multi-Module System
WARNING
!
THE WEIGHT OF A UPS MODULE CAN REACH 22KG, THEREFORE IT IS
RECOMMENDED TO BE LIFTED BY 2 PERSONS. THE MODULE SHALL
NEVER BE CARRIED BY ONE PERSON ONLY
5.2.3.1
How to Extract a Module in a Capacity Multi-Module System
If in capacity parallel system a UPS-Module experiences a fault and there is not enough capacity left to protect
the load by the remaining operating UPS-Modules, the load will automatically be transferred to bypass
(Bypass-Mode or Eco-Mode) and will continue to be supplied by the mains power supply.
To extract the faulty module from the UPS-Frame in a Capacity
Multi-Module
System proceed as follows:
1.
Identify the faulty Module with the Alarm condition and RESET the Alarm. The audible noise will stop.
If the Alarm conditions persists (the LED-Indicator ALARM is red) there is a fault in the UPS-Module.
2.
Verify that the load is on Bypass and is supplied by the mains power (Bypass-Mode or Eco-Mode) on
all UPS-Modules; in the majority of the events the LED-indicators on Control Panel of the Faulty
Module will show:
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
Green
INVERTER
RED
BATTERY
Green
3.
Whereas the LED-indicators on the Control Panels of the other Operating Modules will show
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
Green
INVERTER
OFF
BATTERY
Green
4.
Close Maintenance Bypass Switch IA1 (position ON)
5.
On LCD: “MANUAL BYP IS CLOSED” will appear and the LED
-indicator will indicate as shown
below:
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
Green
INVERTER
RED
BATTERY
Green
The load is now directly supplied by mains and is
not protected
6.
Press both ON/OFF Buttons on UPS-Module to be replaced simultaneously;
7.
Open corresponding battery fuses
8.
Remove the two fixation screws and slide out the UPS-Module (10cm)
This operation will disconnect module by the power connection located on the back of the cabin.
Содержание DPA Upscale M 10
Страница 27: ......
Страница 28: ......
Страница 29: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 51: ......
Страница 52: ......
Страница 53: ......