![ABB ControlMaster CM30 Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/abb/controlmaster-cm30/controlmaster-cm30_user-manual_2344030.webp)
ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
6 Basic Level
28
IM/CM/ED–EN Rev. X
6 Basic Level
The
Basic
menu provides access to the tunable control settings and setpoint
values.
Loop 1 (2) Setpoints
Local
S
etpoint 1 (4)
The local setpoint value required. If this value is adjusted in the
Operator Level
(see page 23)
its value in here is also updated.
R
S
P Ratio
If the remote (external) setpoint is selected the control setpoint value is (ratio x remote
setpoint input) + bias.
Note
. This parameter is available only if the template selected has remote setpoint or if a
ratio controller / station template is selected – see page 94.
R
S
P Bias
Sets the remote setpoint bias in engineering units.
Note
. This parameter is available only if template selected has remote setpoint or ratio.
Ramp Mode
The ramping setpoint facility can be used to prevent a large disturbance to the control
output when the setpoint value is changed. The rate set applies to both the local and the
remote setpoints.
Ramp Rate
Sets the ramp rate required in engineering units / hour.
Note
. Applicable only if
Ramp Mode
is
On
.
Menu
Basic
Exit
Select
100
200
PV
300
0
Displayed Local Setpoint Value
Time
Actual (Ramping) Setpoint Value
used by PID Algorithm*
*Example: Ramp Rate = 200 Increments / Hour
1 Hour