Appendix A – Digital and Analog Sources
A.1 Digital Sources
Note.
Numbers in brackets indicate additional parameters, for example,
Alarm 1 (8) Ack. State
indicates that 8
Alarm Ack. State
parameters are available.
Source Name
Description [Comment]
Alarm 1 (8)
Ack. State
Acknowledged alarm = 0
Unacknowledged alarm = 1
Alarm 1 (8) State
Alarm state
Anlg IP 1 (4) Fail
Analog Input Failure (active when the
signal detected at the analog input is
outside the fault detect level specified
during configuration).
AO1 (2) Loop Break
Analog output
Delay Timer 1 (2)
Delay timer state
IP 1 (4) Digital State
Input 1 (4) digital state
Linearizer 1 (2) Fail
Custom linearizer failure
Logic Equation 1 (8)
Logic equation result
Loop 1 SP Mode
Setpoint mode selected
0 = Local, 1 = Remote
Loop 1 Auto Mode
Automatic control mode
Loop 1 Close Relay
Motorized valve close relay state
Loop 1 LSP 1 (4)
State
Local setpoint state
1 = setpoint selected
Loop 1 Manual
Mode
Manual control mode
1 = Manual
Loop 1 Open Relay
Motorized valve open relay state
Loop 1 TP OP1
Time proportioning output
Loop 1 Valve State
Motorized valve state
Loop 1 Valve Stuck
Motorized valve stuck state
Loop 1 Ctrl Track
Control track state
Math Block 1 (8) Fail
Maths failure
RTA 1 (2) State
Real time alarm state
Softkey Toggle
Front panel soft key toggles the source's
state
Softkey Edge
Front panel soft key sets the source active
on key press
T1 (2) Int Pulse
Totalizer intermediate pulse – active for
1 second when the intermediate count is
reached
T1 (2) Run State
Totalizer run state
1 = Totalizer running
T1 (2) Wrap Pulse
Totalizer wrap pulse
If
Wrap Enable
is
On
– active for 1 second
when the predetermined count is reached
Off
– active when the predetermined
count has been reached and remains
active until the totalizer is reset
Profile Run
1 = Running
Profile Hold
1 = Hold
Profile Holdback
1 = Hold (due to guaranteed Soak/Ramp)
Profile Wait
1 = Wait
Profile Reset
1 = Reset
Profile Prog. End
1 = End (active for 5 seconds)
Profile Seg. End
1 = End (active for 5 seconds)
Profile Event 1
:
8
1 = Event active
Profile PV Event
1 = Event active
Profile Time Event
1 = Event active
Source Name
Description [Comment]