3.2
Storage
The packing of the goods protects it from mechanical and environmental damage. UPS and Battery
cabinets should be store in its original packaging. Make sure that the goods are stored indoor,
protected from water and sunshine in a clean environment.
NOTE!
THE RECOMMENDED TEMPERATURE FOR STORAGE OF THE UPS
SYSTEM AND BATTERIES IS B20 °C AND +25°C, HUMIDITY <
95% (NON-CONDENSING).
FOR UPS SYSTEM ONLY THE STOREAGE TEMPERATURE CAN BE
BETWEEN -25 °C AND +70°C, HUMIDITY < 95% (NON-CONDENSING).
BEFORE SWITCHING ON THE UNIT(S), MAKE SURE THE AMBIENT
TEMPERATURE HAS REACHED THE OPERATION TEMPERATURE RANGE
WHICH IS 0°C - +40°C.
SEALED BATTERIES MUST NEVER BE STORED IN A DISCHARGED OR
PARTIALLY DISCHARGED STATE.
EXTREME TEMPERATURE, UNDER- AND OVERCHARGE AND
OVERDISCHARGE WILL DESTROY BATTERIES!
If the UPS is delivered without batteries, the manufacturer is not responsible for any damage or
malfunctioning caused to the UPS by incorrect wiring. For long-term storage make sure that the
battery is fully recharged every 6 months. Before and after storing, charge the battery.
3.3
Unpacking
Prior unpacking make sure that the floor surface is solid and suitable for supporting the weight of all
the equipment. The UPS and accessories are delivered on a specifically designed pallet that allowing
to move it with a forklift or a pallet jack. Bring the unit(s) close to the end position and unpack them by
removing the packing and shipping materials as described next.
WARNING
CENTER of GRAVITY
WEIGHT (kg)
UPS AND BATTERY CABINETS ARE HEAVY AND TALL. MAKE SURE YOU
ARE ALWAYS WORKING SAFELY BY USING APPROPIRATE TOOLS AND
EQUIPMENT. WHEN MOVING THE UNITS AROUND USING FORKLIFT,
ALWAYS MAKE SURE THE UNITS ARE IN UPRIGHT POSITION AND MOVE
WITH SLOW SPEED AND SLOW ACCELERATIONS.
WHEN MOVING THE EQUIPMENT ALWAYS REFER TO THE CENTER OF
GRAVITY (COG) LABEL. WHICH MAY NOT BE IN ALWAYS IN THE MIDDLE
(SEE FIGURE ON THE LEFT).
DPA 500 EQUIPPED WITH 1-2 MODULES HAVE THE COG IN THE MIDDLE
OR CLOSE TO IT, WHEREAS A DPA 500 WITH 3-5 MODULES HAS THE
SHIFTED TO THE SIDE.
Содержание Conceptpower DPA 500
Страница 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Страница 2: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Страница 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Страница 90: ......
Страница 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...