ABB COM600F ANSI Скачать руководство пользователя страница 31

ExploringGOOSEPackets.png

Figure 6.3.2-1 Exploring GOOSE packets

GOOSE Packets Diagnosis explore the time based view of specific GOOSE packets that
are captured from the network.

Exploring GOOSE events

6.3.3.

To open a new dialog box for the graphical representation of GOOSE events, click the
context menu for Explore GOOSE Events (see Figure 6.3.3-1).

31

COM600 series 5.0

1MRS757546

GOOSE Analyzer Operator's Manual

Содержание COM600F ANSI

Страница 1: ...COM600 series 5 0 GOOSE Analyzer Operator s Manual...

Страница 2: ......

Страница 3: ...Analyzer WebHMI 12 3 4 1 GOOSE Analyzer WebHMI 12 3 4 2 Title bar 13 3 4 3 Menu bar 13 3 4 4 Content page 13 4 GOOSE Connection Viewer 14 4 1 Using GOOSE Connection Viewer 14 4 2 Viewing subnetworks 1...

Страница 4: ...ork analyzer group 37 9 2 2 Intrusion analyzer 37 9 2 3 Statistic analyzer 37 9 3 IED analyzers 38 9 3 1 IED analyzer group 38 9 3 2 GOOSE bus analyzer 38 9 3 3 Statistic analyzer 38 9 4 GOOSE control...

Страница 5: ...license and may be used copied or disclosed only in accordance with the terms of such license Copyright 2012 ABB All rights reserved Trademarks 1 2 ABB is a registered trademark of ABB Group All other...

Страница 6: ...ut of range the following message is displayed Entered value is not valid The value must be 0 30 You can be asked to enter the string MIF349 in a field The string is shown as follows in the procedure...

Страница 7: ...e in the network for example a protection relay Device Change of process data or an OPC internal value Normally an event consists of value quality and timestamp Event A physical IEC 61850 device that...

Страница 8: ...tion SCD Substation Configuration Language SCL Related documents 1 8 MRS number Name of the manual 1MRS756125 COM600 User s Manual 1MRS756705 COM600 Operator s Manual 1MRS756740 COM600 HMI Configurati...

Страница 9: ...o facilitate substation and grid automation solutions in IEC and ANSI market areas a variant based system similar to Relion 615 and 620 series is being followed from COM600 5 0 release The main reason...

Страница 10: ...cation diagnosis enabling features communication status follow up and storing of GOOSE events for auditing purposes GOOSE Analyzer consists of a server and a WebHMI The GOOSE Analyzer server includes...

Страница 11: ...png Figure 3 1 1 GOOSE Analyzer tab on COM600 WebHMI menu bar Logging in to GOOSE Analyzer 3 2 To log in to GOOSE Analyzer 1 Click the GOOSE Analyzer diagnostics Icon in the tool box in GOOSE Analyze...

Страница 12: ...displayed see Figure 3 3 1 2 Click or Logout on the title bar to exit GOOSE Analyzer GOOSELogout jpg Figure 3 3 1 Title bar General overview of GOOSE Analyzer WebHMI 3 4 GOOSE Analyzer WebHMI 3 4 1 Wh...

Страница 13: ...bar 3 4 3 On the menu bar you can see GOOSE Analyzer functionalities see Figure 3 3 1 GOOSE ConnectionViewer shows GOOSE connection views on the content page Historical Events provides means to query...

Страница 14: ...is split into two panels the left panel is a navigation tree and the right panel shows the corresponding connection diagram see Figure 4 1 1 You can use the navigation tree to view the selected GOOSE...

Страница 15: ...s internal GOOSE configuration In Figure 4 1 1 each GOOSE subscriber connects to several existing GOOSE buses with an inward arrow representing different subscriptions to other IEDs Dots are used on t...

Страница 16: ...ighlighting GOOSE connection Exploring GOOSE configuration 4 2 3 To explore the sets of GOOSE signals associated with GOOSE control blocks double click the selected GOOSE bus see Figure 4 2 3 1 Each s...

Страница 17: ...hich means that the subscriber might not be able to receive all GOOSE messages in a defined time interval A GOOSE receiving error might be reported by the subscribing IEDs All timeout unavailability o...

Страница 18: ...licts see Figure 4 2 4 1 For a more detailed explanation of the statuses see 9 2 1 Subnetwork analyzer group Viewing GOOSE connections 4 3 Viewing IED level connections 4 3 1 To view GOOSE connections...

Страница 19: ...gnals click the connection line from the source IED to the destination see Figure 4 3 1 1 Monitoring GOOSE control block status 4 3 2 GOOSE Analyzer can monitor the transmission of specific GOOSE mess...

Страница 20: ...IED level view see Figure 4 5 2 and a detailed view of GOOSE configuration see Figure 4 5 3 To navigate to different views click the IED name in the first column SubnetworkGOOSEConnections png Figure...

Страница 21: ...GOOSEConfigurationDetailedView png Figure 4 5 3 Detailed view of GOOSE configuration 21 COM600 series 5 0 1MRS757546 GOOSE Analyzer Operator s Manual...

Страница 22: ...om of the GOOSE Connection Viewer screen RealtimeEventIndicationBar png Figure 5 2 1 Real time event indication bar To expand the real time event indication bar click the arrow see Figure 5 2 2 The li...

Страница 23: ...has the following properties Detected Time date and time of a diagnostic event Subnetwork subnetwork name IED IED name GOOSE Control Block GOOSE control block reference Object Text descriptive text fo...

Страница 24: ...vents To configure the filter of the displayed list 1 Click Filter The Filter configuration dialog see Figure 5 2 4 appears 2 Select the specific branch to view 3 Click OK or click Cancel to cancel fi...

Страница 25: ...lay of the event list click or respectively see Figure 5 2 2 Using Historical Events 5 3 To view historical events click on Historical Events on the menu bar A new dialog box opens displaying all hist...

Страница 26: ...time event list but its data source is the historical database To query specific events from the database use conditional settings You can reset the query conditions for new queries and export the qu...

Страница 27: ...see the list of all test cases Each test case can be activated to capture the defined GOOSE packets as well as their associated events At the bottom of the left panel you can see the disk consumption...

Страница 28: ...tab opens for creating a test case see Figure 6 2 1 CreatingTesterScript jpg Figure 6 2 1 Creating a tester script 3 Enter a name for the script 4 Select script type Auto or Manual 5 Set the parameter...

Страница 29: ...n of a script select the script and click Start Manual scripts are started immediately while auto scripts are only started when the configured conditions become active To delete a script select the sc...

Страница 30: ...IED GoCB To view associated GOOSE Diagnostic Events and GOOSE Events select a GOOSE control block To explore GOOSE Packets GOOSE Events and GOOSE Diagnosis right click a GOOSE control block entry A c...

Страница 31: ...based view of specific GOOSE packets that are captured from the network Exploring GOOSE events 6 3 3 To open a new dialog box for the graphical representation of GOOSE events click the context menu fo...

Страница 32: ...6 3 4 To open a new dialog box for the graphical representation of GOOSE diagnosis events click the context menu for Explore GOOSE Diagnosis see Figure 6 3 4 1 ExploringGOOSEDiagnosis png Figure 6 3...

Страница 33: ...k Network Statistic on the menu bar The Network Statistic dialog box opens The statistic trend view is structured according to the queried information It provides statistics information on GOOSE packe...

Страница 34: ...y in the Network Statistic tab to plot the correspond ing trend GraphPanel png Figure 7 1 3 Network statistic trend You can compare different trends on the plotting area by clicking a similar trend To...

Страница 35: ...GOOSE Analyzer can be viewed in the Events List in COM600 WebHMI This functionality is used in cases where the GOOSE Analyzer diagnostics WebHMI is not started GATFigure 1 1 1 png Figure 8 1 1 GOOSE...

Страница 36: ...esponding GOOSE Analyzer diagnostic events in COM600 WebHMI Note that only diagnostic events can be viewed in COM600 WebHMI These can be used to verify the health of GOOSE 36 1MRS757546 COM600 series...

Страница 37: ...yzers belong to this group Intrusion analyzer Statistic analyzer Intrusion analyzer 9 2 2 GOOSE intrusion is a GOOSE message whose configuration is not listed in the system configuration It might harm...

Страница 38: ...an problems have been found with GOOSE Analyzer in COM600 see 9 4 7 Timeout flow status analyzer Normal transmission of GOOSE packets is according to its configuration and thus treated as normal marke...

Страница 39: ...ng at all receivers of GOOSE messages This way the analyzer can secure IED performance The allowed GOOSE multicast address range is 01 0C CD 01 00 00 until 01 0C CD 01 FF FF The destination MAC addres...

Страница 40: ...value range for VLAN is 000 to FFF The VLAN ID analyzer compares the VLAN ID contained in the received GOOSE message packet with that in the SCD based on the reference of the GOOSE control block In no...

Страница 41: ...tSet reference analyzer 9 4 8 The attribute DatSet represents the reference of the data set whose values are transmitted The members of the data set are uniquely numbered starting with 1 This number i...

Страница 42: ...UE if the GoCB requires further configuration Further configuration is required in the following cases The attribute DatSet has the value NULL The number or size of values conveyed by the elements in...

Страница 43: ...normal status the DatSet structure conforms to the value in the configuration When a DatSet structure mismatch is detected the analyzer issues a specific diagnostic event to warn users of the status t...

Страница 44: ...44...

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...0 22 11 Fax 358 10 224 1094 ABB Inc Medium Voltage Products 655 Century Point Lake Mary FL 32746 USA Tel 1 407 732 2000 Fax 1 407 732 2335 www abb com medium voltage 1MRS757546 D 24 5 2017 Copyright 2...

Отзывы: