Configuration
3.
About this section
3.1.
This section describes the configuration tasks for HMI.
Operating system access permissions using local
browser
3.2.
When using COM600 browser locally in the COM600 computer, it can be specified
whether the browser locks down the access to the operating system functions for non-
administrator users.
The C:\Program Files\COM610 GW SW\WebBrowser folder in the COM600 computer
contains a
config.ini
file, which has an option called
useLockedMode
. By default it is set
to value 0, which means that no locking is done. When set to 1, the access to operating
system functions is disabled from non-administrator users.
Prerequisites
3.3.
Before you start configuring the HMI, pay attention to the following:
1.
Prepare the communication structure as instructed in COM600 User's Manual.
2.
Make sure that you have the necessary connectivity packages or SCL description
files that can help you in the configuration process.
3.
Outline the Single Line Diagram structure you want to create for your system.
Use the Management function to update the COM600 communication configuration at
least once before you start the substation configuration. If you do not update the config-
uration, the statuses of objects in HMI Single Line Diagram can be bad or uncertain.
To fix the statuses of objects in Single Line Diagram:
1.
Save the substation configuration.
2.
Update the COM600 configuration with the Management function by changing any
property in SLD Editor and by clicking Apply.
3.
Update the COM600 configuration again using with the Management function.
14
1MRS756740
COM600 series, Version 4.1
HMI Configuration Manual
Содержание COM600 series
Страница 1: ...COM600 series Version 4 1 HMI Configuration Manual...
Страница 2: ......
Страница 64: ...64...
Страница 65: ......