When you select the alert icon in the header area, the system asks if you want to return
to the normal switch operation sequence. You can either confirm it or cancel it.
To enable to disable returning to normal switch operation sequence:
1.
In COM600 HMI, select FDIR.
2.
In the FDIR Control dialog, select the FDIR Mode tab.
3.
In the Return to Normal list, select Enable or Disable.
Enabling or disabling changing of protection setting groups
3.2.5.
You can enable or disable changing of protection setting groups during FDIR operation.
If the Setting Group function is enabled, the system will check the load change on the
switch before the FDIR operation. The system will send a change setting group command
to the IED controlling the switch, if necessary.
To enable or disable changing of protection setting groups:
1.
In COM600 HMI, select FDIR.
2.
In the FDIR Control dialog, select the FDIR Mode tab.
3.
In the Group Setting list, select Enable or Disable.
FDIR simulation
3.3.
Simulating faults
3.3.1.
To simulate a fault:
1.
Set the IED to the simulation mode in SAB600 and redownload the configuration
to COM600.
2.
In COM600 HMI, select FDIR.
The FDIR Control dialog opens.
12
1MRS757279
Grid Automation Controller COM600 4.0
FDIR Operation Manual