![ABB COM600 3.4 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/abb/com600-3-4/com600-3-4_user-manual_1209061.webp)
Controllable single point (SPC)
5.2.12.
SPC represents DMCD C_SC_NA_1, C_DC_NA_1, M_SP_NA_1, M_SP_TA_1,
M_SP_TB_1, M_DP_NA_1, M_DP_TA_1, M_DP_TB_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_BOOL
SCO
M
SPI
ctlVal
VT_BOOL
SPI
M
FALSE | TRUE
stVal
VT_I4
BL, SB, NT, IV
M
Quality
q
VT_DATE
CP24Time2A
M
TimeStamp
t
VT_BSTR
O
Text
Description
d
Controllable double point (DPC)
5.2.13.
DPC represents DMCD C_SC_NA_1, C_DC_NA_1, M_SP_NA_1, M_SP_TA_1,
M_SP_TB_1, M_DP_NA_1, M_DP_TA_1, M_DP_TB_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_BOOL
SCO
O
FALSE | TRUE
SPI
ctlOperOn
VT_BOOL
SCO
O
FALSE | TRUE
ctlOperOff
VT_BOOL
SCO
O
FALSE | TRUE
ctlSelOn
VT_BOOL
SCO
O
FALSE | TRUE
ctlSelOff
VT_I4
DPI
M
intermediate-state
(0)
off (1)
on (2)
bad-state (3)
ENUMERATED
stVal
VT_I4
BL, SB, NT, IV
M
Quality
q
VT_DATE
CP24TIME2A
M
TimeStamp
t
VT_BOOL
SCO
O
FALSE | TRUE
BOOLEAN
ctlCan
VT_BOOL
SPI
O
FALSE | TRUE
BOOLEAN
stSeld
VT_BSTR
O
Text
Description
d