Controllable integer status (INC)
3.4.5.14.
Table 3.4.5.14-1 Configurable INC properties for OPC client
Description
Value or Value range/ Default
Property/ Para-
meter
Basic
Common data class according to IEC
61850
INC
Common Data
Class
Addresses
IEC address for command.
0...16777215
Default: 0
Command Address
IEC address for indication.
0...16777215
Default: 0
Indication Address
Common
Class of ASDU. Data sent from the slave
to the master can be assigned to two
classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
class 2.
Class 1 = 1
Class 2 = 2
Default: Class 1 = 1
Class
Interrogation group. 1 - 16 general or 1 -
4 counter interrogation.
1...16 (general) or 1...4 (coun-
ters)
Interrogation Group
Defines whether a new indication value
overwrites an older one in the queue.
True = 1
False = 0
Default: False = 0
Over Write
Priority of ASDU. This property defines
how the ASDU sent is placed in the class
1 and class 2 queues.
0...3
End of queue = 0
Middle = 1, 2
Beginning of queue = 3
Priority
Maximum update rate of indication
changes between OPC server and client
in milliseconds. 0 means that server sends
all the changes to the client.
0...60000
Default: 0
Update Rate
Data Class Spe-
cific
Send value of indication signal as normal-
ized or scaled. Long timestamp format
cannot be used with a scaled value.
Send with normalized value =
0
Send with scaled value = 1
Send Indication As
Value Type
48
1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual