Appendix : List of CBV-2U4-3T(-N) points
The
CBV-2U4-3T
strategy
is available in both Imperial and Metric units.
The tables in this Appendix list and describe the points in the
Strategy
, and gives the units in each
Strategy
type
along with the default value in that
Strategy
type.
HARDWARE POINTS (I/O)
ANALOG
POIN
T
POINT TYPE
OBJECTNA
ME
DESCRIPTION
IMPERIA
L
UNITS
METRI
C
UNITS
1
Analog Input
UI01
Room/Zone Temperature Sensor
° F
° C
2
Analog Input
UI02
Setpoint Adjust Potentiometer
Ohms
Ohms
3
Analog Input
UI03
Supply or Discharge Air Temperature
° F
° C
4
Analog Input
UI04
CO2, Humidity, or Motion Detection
Volts
Volts
8
Analog Input
UI08
Flowrate Sensor
Pascals
Pascals
14
Analog
Output
AO14
Modulating Heat Stage 1
%
%
15
Analog
Output
AO15
Modulating Heat Stage 2 or Variable Fan
Speed Control
%
%
16
Analog
Output
AO16
Damper Command Position
(CBV-2U4-3T ONLY)
%
%
DIGITAL
POINT POINT TYPE
OBJECTNAME DESCRIPTION
Active
Text
Inactive
Text
9
Digital
Output
DO09
Actuator Clockwise Output
(CBV-2U4-3T-N ONLY)
On
Off
10
Digital
Output
DO10
Actuator Counter-Clockwise Output
(CBV-2U4-3T-N ONLY)
On
Off
11
Digital
Output
DO11
Heating Stage 1 or Tri-State Heating Valve
Open
On
Off
12
Digital
Output
DO12
Heating Stage 2 or Tri-State Heating Valve
Close
On
Off
13
Digital
Output
DO13
Heating Stage 3 or Single Speed Fan
On
Off