Installation
44
One (1) CSU con-
nected
If there is one (1) CSU connected to the CSU input X1, 21 then set the DIP
switch 1 to position ON.
Two (2) CSU con-
nected
If there are two (2) CSUs connected to the CSU input 21 and 22 then set the
DIP switch 1 and 2 to position ON.
Note!
The CSU cable is connected before configuration is made.
For more information how to connect CSU cables, see the chapter “Con-
necting CSU cable” on page - 34.
O
N
1 2
3 4 5 6 7 8
O
N
1 2
3 4 5 6 7 8