![ABB Advant Controller 450 Скачать руководство пользователя страница 219](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016219.webp)
Advant
®
Controller 450 User’s Guide
Section 2.4.2 Controller and I/O
3BSE 002 415R701 Rev A
2-65
2.4.2.7 Summary of the Controller Start-up and Verification of the Start
The following summary is a basic “from scratch” step-by-step instruction explaining how to
start up. Other working schedules exist, especially in connection to revisions and system
enlargement. Please refer to the reference manual AMPL Configuration Advant Controller 400
Series for complete information.
1.
Power up
Set start mode to 3 (CLEAR) on processor module
Set power switch on
For indications which verify a successful power-up, see
.
2.
Working mode CONFIGURATION
Automatically enter the working mode CONFIGURATION at power-up
Then set start mode selector in position 1 (AUTO). No ENTER
Processor module indicates P2 (working mode CONFIGURATION).
3.
Controller system configuration
a.
Dimensioning of data base, DIMDB
b.
Creating the data base, CRDB
c.
Data entry of data base, MDB
d.
Dumping and loading (compress) the data base, DUTDB/LOTDB
e.
Dimensioning of PC program tables, DIMPC (have to be done to enable update of
I/O signals).
4.
Configuration/application building
a.
Populating the data base, MDB
b.
Entering and editing PC program, miscellaneous commands
c.
Dumping and loading PC programs, DUTPT/LOTPT.
5.
Backup of the entire RAM, DUAP.
6.
Disabling working mode CONFIGURATION, DICONFIG.
In addition to those indications obtained at power-up:
–
All red LED F (Fault) on S100 I/O board fronts are switched off.
–
The yellow LEDs INIT and INHIB on S100 I/O Bus Extenders DSBC 174/
DSBC 176 board front are switched off.
–
The processor module changes over and indicates P1 (working mode OPERATION).
The system is now started and ready for operation.
Perform the final stages, which include start of application program execution, successively and
relate to the product verification. One PC program at a time.
WARNING
When the application program is started, the process to be controlled is
influenced.
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...