Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-4
3BSE 002 415R701 Rev A
2.1.3.1 Summary of CE-marking Aspects
CE-marking of the Advant OCS products implies some minor but important changes of the
design with respect to cabinetry, mains supply filtering and handling of cable shields. All to
ensure conformity to the EMC-Directive 89/336/EEC.
The following is a summary of the most important changes.
Cabinet Floor Cover Plates
From an EMC Viewpoint mounting of floor cover plates is not necessary when EMC standard
cabinets of the types RM5xx and RH5xx is applied. The close distance to the normally good
floor earth plane is the reason.
Avoid the erection of fixed installed radio equipment close to and beneath the Advant
Controller. For example in underlying floor plane.
The floor cover plates may be mounted by any other reason determined in the particular project.
Cabinetry
According to information given in the ordering documentation, Advant Controller 450 shall be
located in a EMC-proof cabinetry. Please note that the requirement is valid to controller cabinet,
I/O cabinet and connection unit cabinet, if separated.
Standard cabinet RM500 is EMC-proof in its basic design for protection class IP21, IP41,
and IP54.
Open compartment is not permitted for any part of the controller and its I/O including
distributed connection units.
Immunity against electromagnetic fields can generally be guaranteed with the cabinet
containing metallic doors only.
Arrangement of Cabinets
Advant OCS mounted in a RM500 cabinet, can be set up side by side with other cabinet types
and other equipment types, but the cabinet side plates must be ordered or not be removed if
included at the delivery.
Where several electronics cabinets of the same type, related to one controller with
S100 I/O, are to be set up in the same row, however, it is permissible to leave out or remove the
side plates between the cabinets.
Mains Net Filter
Protection against line conducted radio emissions is obtained by means of a special filter placed
in the bottom part of the cabinet on the incoming supply. One filter for each supply is utilized.
Communication Cable Shields
Communication cable shields which are to be directly grounded in the cabinet must be grounded
to the cabinet chassis.
Shielded communication cables which are not directly grounded in the cabinet are to be
connected via a capacitive decoupling device, located in the bottom of the cabinet.
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...