Parameter
Specification
Ambient temperature
Power Output [%]
De-rating [%]
[°C]
[°F]
-35 ... + 35
-31 … +95
100
0
+ 36 … + 40
+96 …+104
100
0
+ 41 … + 45
+105 …+113
93
7
+ 46 … + 50
+114 …+122
80
20
+ 51 … + 55
+123 …+131
67
33
The output power of the EVSE can be limited by the temperature of the charge
connector. This limitation can be caused by the connector model and rating, the EV
socket rating and the ambient conditions.
10.15
Harmonics on the grid
10.15.1
Terra 184
Working
point
Electric
load
V
thd
(L1/L2/L3)
I
thd
(L1/L2/L3)
900 V /
200 A
100 %
0.669 % 0.638 % 0.698 % 3017 %
3070 %
2984 %
Order
Phase L1
Phase L2
Phase L3
IRMS
HDF
IRMS
HDF
IRMS
HDF
[A]
[%]
[A]
[%]
[A]
[%]
1
225.10
100.00
225.25
100.00
225.04
100.00
2
0.17
0.07
0.66
0.30
0.64
0.29
3
0.57
0.25
0.52
0.23
1.08
0.48
4
0.42
0.19
0.17
0.08
0.34
0.15
5
6.06
2.69
6.21
2.76
5.76
2.56
6
0.23
0.10
0.25
0.11
0.53
0.24
7
2.07
0.92
1.93
0.86
2.08
0.93
8
0.35
0.15
0.18
0.08
0.21
0.09
9
0.19
0.08
0.14
0.06
0.13
0.06
10
0.05
0.02
0.04
0.02
0.09
0.04
11
0.36
0.16
0.31
0.14
0.42
0.19
12
0.26
0.11
0.16
0.07
0.31
0.14
13
0.63
0.28
0.75
0.33
0.57
0.26
14
0.26
0.11
0.15
0.07
0.24
0.11
15
0.01
0.01
0.17
0.08
0.16
0.07
16
0.20
0.09
0.39
0.18
0.30
0.13
17
0.85
0.38
0.78
0.35
0.76
0.34
18
0.25
0.11
0.27
0.12
0.47
0.21
Technical data
9AKK108466A3703-EN | 001