Standard function blocks
404
Timers
MONO
(10057)
Illustration
Execution time
1.46 µs
Operation
The output (O) is set to 1 and the timer is started, if the input (I) is set to 1. The output is
reset to 0 when the time defined by the time pulse input (TP) has elapsed. Elapsed time
(TE) count starts when the output is set to 1 and stops when the output is set to 0.
If RTG is 0, a new input pulse during the time defined by TP has no effect on the
function. The function can be restarted only after the time defined by TP has elapsed.
If RTG is 1, a new input pulse during the time defined by TP restarts the timer and sets
the elapsed time (TE) to 0.
Example 1: MONO is not re-triggable, i.e. RTG = 0.
Example 2: MONO is re-triggable, i.e. RTG = 1.
Inputs
Re-trigger input (RTG): Boolean
Time pulse input (TP): DINT (1 =
µs)
Input (I): Boolean
Outputs
Output (O): Boolean
Time elapsed output (TE): DINT (1 = 1 µs)
MONO
85
TLA1 1 msec
(1)
RTG
TP
I
O
O(85)
TE
TE(85)
I
O
RTG = 0, TP = 4 s
0
1
t / s
2
3
4
5
6
7
8
9
10
4 s
4 s
TE = 0 s
TE = 4 s
TE = 0 s
TE = 4 s
TE = 0 s
I
O
RTG = 1, TP = 2 s
0
1
t / s
2
3
4
5
6
7
8
9
10
2 s
TE = 0 s
TE = 2 s
* TE is set to 0.
*
*
*
*
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...