Standard function blocks
356
DINT_TO_REALn_SIMP
(10022)
Illustration
Execution time
6.53 µs
Operation
The output (O) is the REAL/REAL24 equivalent of the input (I) divided by the scale input
(SCALE).
Error codes indicated at the error output (ERRC) are as follows:
Example (from DINT to REAL24):
When I = 205 and SCALE = 100, I/SCALE = 205 /100 = 2.05 and O = 2.04999.
Inputs
Input (I): DINT
Scale input (SCALE): DINT
Outputs
The output data type is selected by the user.
Output (O): REAL, REAL24
Error output (ERRC): DINT
DINT_TO_REALn_SIMP
(REAL)
86
TLA1 1 msec
(1)
I
SCALE
O
O(86)
ERRC
ERRC(86)
Error code
Description
0
No error
1001
The calculated REAL/REAL24 value exceeds the minimum value of
the selected data type range. The output is set to the minimum value.
1002
The calculated REAL/REAL24 value exceeds the maximum value of
the selected data type range. The output is set to the maximum
value.
1003
The SCALE input is 0. The output is set to 0.
1004
Incorrect SCALE input, i.e. the scale input is < 0 or is not a factor of
10.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...