![ABB ACSM1 Series Скачать руководство пользователя страница 355](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326355.webp)
Standard function blocks
355
DINT_TO_INT
(10021)
Illustration
Execution time
0.53 µs
Operation
The output (O) value is a 16-bit integer value of the 32-bit integer input (I) value.
Examples:
Inputs
Input (I): DINT
Outputs
Output (O): INT
DINT_TO_REALn
(10023)
Illustration
Execution time
7.25 µs
Operation
The output (OUT) is the REAL/REAL24 equivalent of the input (IN). Input IN1 is the
integer value and input IN2 is the fractional value.
If one (or both) of the input values is negative, the output value is negative.
Example (from DINT to REAL):
When IN1 = 2 and IN2 = 3276, OUT = 2.04999.
The output value is limited to the maximum value of the selected data type range.
Inputs
Input (IN1, IN2): DINT
Outputs
The output data type is selected by the user.
Output (OUT): REAL, REAL24
DINT_TO_INT
84
TLA1 1 msec
(1)
I
O
O(84)
I
(31 bits + sign)
O
(15 bits + sign)
2147483647
32767
-2147483648
-32767
0
0
DINT_TO_REALn
(REAL)
85
TLA1 1 msec
(1)
IN1
IN2
OUT
OUT(85)
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...