Parameters and firmware blocks
105
Group
06 DRIVE STATUS
06
6.01
STATUS WORD 1
(page
)
Status word 1.
Bit
Name
Val.
Information
0
READY
1
Drive is ready to receive start command.
0
Drive is not ready.
1
ENABLED
1
External run enable signal is received.
0
No external run enable signal is received.
2
STARTED
1
Drive has received start command.
0
Drive has not received start command.
3
RUNNING
1
Drive is modulating.
0
Drive is not modulating.
4
EM OFF (OFF2)
1
Emergency OFF2 is active.
0
Emergency OFF2 is inactive.
5
EM STOP
(OFF3)
1
Emergency stop OFF3 (ramp stop) is active.
0
Emergency OFF3 is inactive.
6
ACK STARTINH
1
Start inhibit is active.
0
Start inhibit is inactive.
7
ALARM
1
An alarm is active. See chapter
.
0
No alarm
8
EXT2 ACT
1
External control EXT2 is active.
0
External control EXT1 is active.
9
LOCAL FB
1
Fieldbus local control is active.
0
Fieldbus local control is inactive.
10
FAULT
1
A fault is active. See chapter
.
0
No fault
11
LOCAL PANEL
1
Local control is active, ie, drive is controlled from PC tool or con-
trol panel.
0
Local control is inactive.
12
NOT FAULTED
1
No fault
0
A fault is active. See chapter
.
13…15 Reserved
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...