Parameters and firmware blocks
148
48.05
R BR
FW block:
(see above)
Defines the resistance value of the brake resistor. The value is used for brake chopper protection.
0.1…1000 ohm
Resistance.
48.06
BR TEMP FAULTLIM
FW block:
(see above)
Selects the fault limit for the brake resistor temperature supervision. The value is given in percent of
the temperature the resistor reaches when loaded with the power defined by parameter
When the limit is exceeded the drive trips on fault BR OVERHEAT.
0…150%
Resistor temperature fault limit.
48.07
BR TEMP ALARMLIM
FW block:
(see above)
Selects the alarm limit for the brake resistor temperature supervision. The value is given in percent of
the temperature the resistor reaches when loaded with the power defined by parameter
When limit is exceeded the drive generates alarm BR OVERHEAT.
0…150%
Resistor temperature alarm limit.