534 Fault tracing
73B1
Stop failed
Ramp stop did not finish within
expected time.
Check the settings of parameters
.
Check the predefined ramp times in
parameter group
.
73F0
Overfrequency
Maximum allowed output
frequency exceeded.
Without a dual-use license, the fault limit
is 598 Hz. Contact your local ABB
representative for dual-use licensing
information.
7510
FBA A communication
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups
and
.
Check cable connections.
Check if communication master is able to
communicate.
7520
FBA B communication
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module B or between
PLC and fieldbus adapter
module B is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter group
Check cable connections.
Check if communication master is able to
communicate.
7580
INU-LSU comm loss
Programmable fault:
DDCS (fiber optic)
communication between
converters (for example, the
inverter unit and the supply
unit) is lost.
Check status of other converter
(parameter group
).
Check settings of parameter group
. Check the
corresponding settings in the control
program of the other converter.
Check cable connections. If necessary,
replace cables.
7581
DDCS controller
comm loss
Programmable fault:
DDCS controller comm
loss function
DDCS (fiber optic)
communication between drive
and external controller is lost.
Check status of controller. See user
documentation of controller.
Check settings of parameter group
Check cable connections. If necessary,
replace cables.
7582
MF comm loss
Programmable fault:
Master/follower
communication is lost.
See
).
7583
Line side unit faulted
The supply unit (or other
converter) connected to the
inverter unit has generated a
fault.
The auxiliary code specifies the original
fault code in the supply unit control
program. See section
(page
Code
(hex)
Fault
Cause
What to do
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...