Parameter settings 23
Inverter units parameter settings
The inverter unit parameter setting in ACS880 primary control program:
•
parameter
31.22 STO indication run/stop
is set to value
Warning/Warning
.
We recommend that you do not set parameter
31.22 STO indication run/stop
to value
0
,
1
or
2
.
This prevents the inverter units from making a fault every time the FSO module
activates the inverter units STO function.
For more information, see the firmware manual.
Safety pulse encoder parameters
The inverter unit parameter settings in ACS880 primary control program when you use a
safety pulse encoder:
•
parameter
90.41 Motor feedback selection
is set to value
Encoder 1
.
•
parameter
90.45 Motor feedback fault
is set to value
Warning
.
Note
: If you want that the inverter units trip on encoder faults, set this parameter to
value
Fault
. For more information, see the firmware manual.
•
parameter
92.21 Encoder cable fault mode
is set to value
A+, A1, B+,B-, Z+
,
Z-
.
92.02 Encoder 1 source Module 1
Sets the safety pulse encoder interface module that the
safety pulse encoder 1 is connected to.
92.10 Pulses/revolution 2048
Sets the number of HTL pulses per revolution for safety
pulse encoder 1.
Adjust the default value to meet the safety pulse encoder in
use. Make sure that the value is according to the encoder
nameplate.
92.17 Accepted pulse
freq of encoder 1
300 kHz
Sets the maximum pulse frequency range of encoder 1.
Adjust the default value to meet the motor and safety pulse
encoder in use. You can use this formula to define the value:
r_max x p 10%, where
• r_max = the maximum motor speed used in the application
(or the motor nominal speed)
• ppr_enc = Pulses/revolution of the safety pulse encoder
(parameter
Index
Name
Example
value
Description