What to do
Cause
Event name /
Aux. code
Code
(hex)
Let chopper cool down.
Brake chopper IGBT temperature has
exceeded internal warning limit.
BC IGBT
excess
temperature
A79C
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling
of the cabinet.
Check resistor overload protection
function settings (parameters
…
Check minimum allowed resistor value
for the chopper being used.
Check that braking cycle meets
allowed limits.
Check that drive supply AC voltage is
not excessive.
Check mechanical brake connection.
Status of mechanical brake
acknowledgement is not as expected
during brake close.
Mechanical
brake closing
failed
A7A1
Check mechanical brake settings in
parameter group
Check that acknowledgement signal
matches actual status of brake.
Check mechanical brake connection.
Status of mechanical brake
acknowledgement is not as expected
during brake open.
Mechanical
brake opening
failed
A7A2
Check mechanical brake settings in
parameter group
Check that acknowledgement signal
matches actual status of brake.
Check mechanical brake settings in
parameter group
Open conditions of mechanical brake
cannot be fulfilled (for example, brake
Mechanical
brake opening
not allowed
A7A5
(especially
has been prevented from opening by
parameter
Check that acknowledgement signal
(if used) matches actual status of
brake.
Check the auxiliary code (format XX00
00YY). “XX” specifies the number of
The hardware current/voltage setting
of an analog input (on an I/O
Extension AI
parameterization
A7AA
the I/O extension module (01:
extension module) does not
correspond to parameter settings.
parameter group
, 02:
, 03:
). “YY”
specifies the analog input on the
module.
For example, in case of I/O extension
module 1, analog input AI1 (auxiliary
code 0000 0101), the hardware
current/voltage setting on the module
is shown by parameter
. The
corresponding parameter setting is
. Adjust either the hardware
setting on the module or the
parameter to solve the mismatch.
Fault tracing 683
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...