Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
10 = 1 / 100 = 1
Underload curve point 1.
-30000.00 ...
30000.00
0.00 / real32
Defines underload curve point 2 load limit active at
corresponding speed set in parameter
Underload curve
point 2
79.22
10 = 1 / 100 = 1
Underload curve point 2.
-30000.00 ...
30000.00
0.00 / real32
Defines underload curve point 3 load limit active at
corresponding speed set in parameter
Underload curve
point 3
79.23
10 = 1 / 100 = 1
Underload curve point 3.
-30000.00 ...
30000.00
0.00 / real32
Defines underload curve point 4 load limit active at
corresponding speed set in parameter
.
Underload curve
point 4
79.24
10 = 1 / 100 = 1
Underload curve point 4.
-30000.00 ...
30000.00
0.00 / real32
Defines underload curve point 5 load limit active at
corresponding speed set in parameter
.
Underload curve
point 5
79.25
10 = 1 / 100 = 1
Underload curve point 5.
-30000.00 ...
30000.00
1.000 / real32
Defines multiplier coefficient applied to the underload
limit calculated out of the underload curve.
Underload curve
scale coef
79.28
10 = 1 / 1000 = 1
Underload curve scale coef.
-30.000 ... 30.000
0.00 / real32
Defines offset additive value applied to the underload
limit calculated out of the underload curve.
Underload curve
offset
79.29
10 = 1 / 100 = 1
Underload curve offset.
-30000.00 ...
30000.00
10.00% / real32
Defines speed reference change in percent relative to
the production speed used at the moment when
underload condition was detected.
The new calculated speed is then used in course of the
underload recovery routine as first step in response to
the underload condition. If the value is set to 0, the
speed boost step is skipped from recovery routine.
Recovery speed
boost
79.31
10 = 1% / 100 = 1%
Recovery speed boost.
0.00 ... 1200.00%
25.00 Hz / real32
Defines absolute speed reference used in course of the
underload recovery routine as a second step after
recovery speed boost.
If the value is set to 0, the speed drop step is skipped
from recovery routine.
Recovery speed drop
ref
79.32
10 = 1 Hz / 100 = 1 Hz
Recovery speed drop reference.
0.00 ... 598.00 Hz
60.0 s / real32
Defines time for a single recovery routine step.
The recovery speed reference change will be active for
the period of time set in this parameter.
Recovery cycle time
79.33
10 = 1 s / 10 = 1 s
Recovery cycle time in seconds.
0.0 ... 30000.0 s
540 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...