Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
None / uint32
Defines a target for the data received as word 3 from
the first follower (ie. the follower with node address 2)
through the master/follower link.
See also parameter
62.30 Follower node 2 data 3 value
.
For the selections, see parameter
.
Follower node 2 data
3 sel
62.6
Follower SW / uint32
Defines a target for the data received as word 1 from
the second follower (ie. the follower with node address
3) through the master/follower link.
See also parameter
62.31 Follower node 3 data 1 value
.
For the selections, see parameter
.
Follower node 3 data
1 sel
62.7
None / uint32
Defines a target for the data received as word 2 from
the second follower (ie. the follower with node address
3) through the master/follower link.
See also parameter
62.32 Follower node 3 data 2 value
.
For the selections, see parameter
.
Follower node 3 data
2 sel
62.8
None / uint32
Defines a target for the data received as word 3 from
the second follower (ie. the follower with node address
3) through the master/follower link.
See also parameter
62.33 Follower node 3 data 3 value
.
For the selections, see parameter
.
Follower node 3 data
3 sel
62.9
Follower SW / uint32
Defines a target for the data received as word 1 from
the third follower (ie. the follower with node address
4) through the master/follower link.
See also parameter
62.34 Follower node 4 data 1 value
.
For the selections, see parameter
.
Follower node 4
data 1 sel
62.10
None / uint32
Defines a target for the data received as word 2 from
the third follower (ie. the follower with node address
4) through the master/follower link.
See also parameter
62.35 Follower node 4 data 2 value
.
For the selections, see parameter
.
Follower node 4
data 2 sel
62.11
None / uint32
Defines a target for the data received as word 3 from
the third follower (ie. the follower with node address
4) through the master/follower link.
See also parameter
62.36 Follower node 4 data 3 value
.
For the selections, see parameter
.
Follower node 4
data 3 sel
62.12
- / uint16
(Follower only) Displays, in integer format, the data
received from the master as word 1.
Parameter
can be used to
select a target for the received data. This parameter
can also be used as a signal source by other
parameters.
M/F data 1 value
62.25
- / -
Data received as word 1 in master/follower
communication.
0...65535
Parameters 511
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...