Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
No / uint16
Enables/disables local control (start and stop buttons
on the control panel, and the local controls on the PC
tool).
WARNING!
Before disabling local control, ensure that the
control panel is not needed for stopping the
drive.
Local control disable
19.17
0
Local control enabled.
No
1
Local control disabled.
Yes
Rpm / uint16
Selects the reference type for scalar motor control
mode.
See also section
, and parameter
Note: This parameter cannot be changed while the
drive is running.
Scalar control
reference unit
19.20
0
Hz. The reference is taken from parameter
(output of the frequency
control chain).
Hz
1
Rpm. The reference is taken from parameter
(speed reference after ramping and
shaping).
Rpm
278 Parameters