Technical data 35
Safety block diagrams
The safety block diagrams show the components that are included in the safety data
calculations. The temperature sensor(s) and protection relay(s) are not included in the
calculations.
One-channel digital input
Two-channel digital input
Response times
The response time of the Safe disconnection (STO) function is < 50 ms for all ACS880
drives. For the exact response times for each drive/inverter module type, see the drive/
inverter module hardware manual.
When the function contains the FSO module, the response time of the Safe disconnection
function is < 100 ms.
Customer
motor
sensor(s)
Drive STO
FSO module
Protection
relay(s)
FSE module
(optional)
Customer
motor
sensor(s)
Drive STO
FSO module
Protection
relay(s)
FSE module
(optional)
Содержание ACS880 Series
Страница 4: ......
Страница 12: ...12 Introduction...
Страница 32: ...32 Parameter settings...
Страница 37: ...Technical data 37 ATEX certificate...
Страница 38: ...38 Technical data...
Страница 39: ...Technical data 39...
Страница 42: ...42 Technical data...
Страница 44: ...www abb com drives www abb com drivespartners 3AUA0000132231 Rev D EN 2018 06 13 Contact us...