What to do
Cause
Event name /
Aux. code
Code
(hex)
Check the auxiliary code, The code
contains location information,
especially with parallel-connected
inverter modules.
When converted into a 32-bit binary
number, the bits of the code indicate
the following:
31…28: Number of faulty inverter
module (0…11 decimal). 1111: STO_ACT
states of control unit and inverter
modules in conflict
27: STO_ACT state of inverter modules
26: STO_ACT state of control unit
25: STO1 of control unit
24: STO2 of control unit
23…12: STO1 of inverter modules 12…1
(Bits of non-existing modules set to
1)
11…0: STO2 of inverter modules 12…1
(Bits of non-existing modules set to
1)
Check safety circuit connections. For
more information, see appropriate
Safe torque off function is active, ie.
STO circuit 2 is broken.
Safe torque
off 2 loss
FA82
drive hardware manual and
description of parameter
indication run/stop (page 320)
.
Check the auxiliary code, The code
contains location information,
especially with parallel-connected
inverter modules.
When converted into a 32-bit binary
number, the bits of the code indicate
the following:
31…28: Number of faulty inverter
module (0…11 decimal). 1111: STO_ACT
states of control unit and inverter
modules in conflict
27: STO_ACT state of inverter modules
26: STO_ACT state of control unit
25: STO1 of control unit
24: STO2 of control unit
23…12: STO1 of inverter modules 12…1
(Bits of non-existing modules set to
1)
11…0: STO2 of inverter modules 12…1
(Bits of non-existing modules set to
1)
Contact your local ABB representative.
SW internal malfunction.
STO
diagnostics
failure
FA90
Memory unit
missing
FB11
•
Power down the control unit.
Check that the memory unit is
properly inserted into the control
unit.
•
No memory unit is attached to
the control unit.
•
The memory unit attached to the
control unit is empty.
Fault tracing 593
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...