Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Control of the supply unit of the drive, such as DC
voltage and reactive power reference.
LSU control
94
Note that the references defined here must also be
selected as the reference source in the supply control
program to be effective.
This group is only visible when supply unit control has
been activated by parameter
.
See also section
On / uint16
Enables/disables the internal INU-LSU state machine.
When the state machine is enabled, the inverter unit
(INU) controls the supply unit (LSU) and prevents the
inverter unit from starting until the supply unit is ready.
LSU Control
94.1
When the state machine is disabled, the status of the
supply unit is ignored by the inverter unit.
0
INU-LSU state machine disabled.
Off
1
INU-LSU state machine enabled.
On
Disable / uint16
Enables/disables control panel and PC tool access to
the supply unit (line-side converter) via the inverter unit
(motor-side converter).
LSU panel
communication
94.2
Note: This feature is only supported by the following
drives:
• ACS880-11
• ACS880-31
• ACS880-17 based on an integrated drive module
• ACS880-37 based on an integrated drive module.
0
Control panel and PC tool access to supply unit via
inverter unit disabled.
Disable
1
Control panel and PC tool access to supply unit via
inverter unit enabled.
Enable
15 s / uint16
Defines the maximum time the supply unit (LSU) is
allowed for charging before a fault,
is generated.
LSU max charging
time
94.10
1 = 1 s / 1 = 1 s
Maximum charging time.
0...65535 s
600.0 s / uint16
Defines a stop delay for the supply unit. This parameter
can be used to delay the opening of the main
breaker/contactor when a restart is expected.
LSU stop delay
94.11
10 = 1 s / 10 = 1 s
Supply unit stop delay.
0.0 ... 3600.0 s
- / real32
(Only visible when IGBT supply unit control activated
by
DC voltage reference
94.20
Displays the DC voltage reference sent to the supply
unit.
Note: This parameter is read-only.
10 = 1 V / 10 = 1 V
DC voltage reference sent to supply unit.
0.0 ... 2000.0 V
504 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...