Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
6
Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Abs both
No action / uint16
Selects the action the drive takes when the value
monitored by signal supervision 3 exceeds its limits.
Note: This parameter does not affect the status
indicated by
.
Supervision 3 action
32.26
0
No action taken.
No action
1
A warning (
) is generated.
Warning
2
The drive trips on
.
Fault
3
If running, the drive trips on
.
Fault if running
Zero / uint32
Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter
.
Supervision 3 signal
32.27
0.000 s / real32
Defines a filter time constant for the signal monitored
by signal supervision 3.
Supervision 3 filter
time
32.28
1000 = 1 s / 1000 = 1
s
Signal filter time.
0.000 ... 30.000 s
0.00 / real32
Defines the lower limit for signal supervision 3.
Supervision 3 low
32.29
- / -
Low limit.
-21474830.00 ...
21474830.00
0.00 / real32
Defines the upper limit for signal supervision 3.
Supervision 3 high
32.30
- / -
Upper limit.
-21474830.00 ...
21474830.00
Parameters 331
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...