62 Planning the electrical installation
Selecting the control cables
Shielding
Use only shielded control cables.
Use a double-shielded twisted pair cable (figure
a
below) for analog signals. Use one
individually shielded pair for each signal. Do not use common return for different
analog signals.
A double-shielded cable (figure
a
) is the best alternative for low-voltage digital
signals, but a single-shielded twisted pair cable (figure
b
) is also acceptable.
Signals in separate cables
Run analog and digital signals in separate, shielded cables.
Do not mix 24 V AC/DC and 115/230 V AC signals in the same cable.
Signals run in the same cable
If their voltage does not exceed 48 V, relay-controlled signals can be run in the same
cables as digital input signals. The relay-controlled signals should be run as twisted
pairs.
Relay cable
The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL,
Germany) was tested and approved by ABB.
Control panel cable
In remote use, the cable connecting the control panel to the drive must not exceed
100 m (330 ft). If multiple panels or drives are connected, the total length of the panel
bus must not exceed 100 m (330 ft).
The cable type tested and approved by ABB is used in control panel option kits.
Suitable cables are CAT 5e unshielded or shielded twisted pair cables.
a
b
Содержание ACS880-M04
Страница 1: ...ABB machinery drives Hardware manual ACS880 M04 drive ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Safety instructions ...
Страница 28: ...28 About the manual ...
Страница 38: ...38 Operation principle and hardware description ...
Страница 48: ...48 Planning the cabinet installation ...
Страница 54: ...54 Mechanical installation ...
Страница 72: ...72 Planning the electrical installation ...
Страница 98: ...98 Electrical installation ...
Страница 102: ...102 Start up ...
Страница 108: ...108 Maintenance ...
Страница 140: ...140 Technical data ...
Страница 158: ...158 Mains chokes ...
Страница 164: ...164 EMC filters 7 Attach the terminal blocks to the filter 1 6 5 4 3 ...
Страница 166: ...166 EMC filters 6 Attach the terminal blocks to the filter 1 2 3 4 ...
Страница 168: ...168 EMC filters ...
Страница 182: ...Dimension drawings 182 Frame size R1 H1 H2 W D ...
Страница 183: ...Dimension drawings 183 Frame size R2 H2 H1 W D ...
Страница 184: ...Dimension drawings 184 Frame size R3 D W H1 H2 ...
Страница 185: ...Dimension drawings 185 Frame size R4 W H1 H2 D ...
Страница 187: ...187 Dimension drawings EMC filters type JFI x1 JFI A1 ...
Страница 188: ...Dimension drawings 188 JFI B1 ...
Страница 189: ...189 Dimension drawings EMC filters type JFI 0x ...
Страница 191: ...191 Dimension drawings Brake resistors type JBR xx ...
Страница 193: ...193 Dimension drawings ...
Страница 195: ...www abb com drives www abb com drivespartners 3AXD50000028613 Rev A EN 2016 04 11 Contact us ...