Planning the electrical installation 59
Alternative power cable types
The recommended and the not allowed power cable types to be used with the drive
are presented below.
Recommended power cable types
Power cable types for limited use
Not allowed power cable types
Symmetrical shielded cable with three phase conductors and a
concentric PE conductor as the shield. The shield must meet the
requirements of IEC 61439-1, see page
. Check with
local/state/country electrical codes for allowance.
Symmetrical shielded cable with three phase conductors and a
concentric PE conductor as the shield. A separate PE conductor is
required if the shield does not meet the requirements of IEC 61439-1,
see page
.
Symmetrical shielded cable with three phase conductors and
symmetrically constructed PE conductor, and a shield. The PE conductor
must meet the requirements of IEC 61439-1, see page
A four-conductor system (three phase conductors and a protective
conductor on a cable tray) is
not allowed for motor cabling
(it is
allowed for input cabling).
A four-conductor system (three phase conductors and a PE conductor in
a PVC conduit) is
allowed for input cabling with phase conductor
cross-section less than 10 mm
2
(8 AWG) or motors < 30 kW (40 hp)
.
Not allowed in the USA.
Corrugated or EMT cable
with three phase conductors and a protective
conductor is allowed for motor cabling with phase conductor cross
section less than 10 mm
2
(8 AWG) or motors < 30 kW (40 hp).
Symmetrical shielded cable with individual shields for each phase
conductor is not allowed on any cable size for input or motor cabling.
PE
PE
PE
PE
PVC
EMT
PE
Содержание ACS880-M04
Страница 1: ...ABB machinery drives Hardware manual ACS880 M04 drive ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 20: ...20 Safety instructions ...
Страница 28: ...28 About the manual ...
Страница 38: ...38 Operation principle and hardware description ...
Страница 48: ...48 Planning the cabinet installation ...
Страница 54: ...54 Mechanical installation ...
Страница 72: ...72 Planning the electrical installation ...
Страница 98: ...98 Electrical installation ...
Страница 102: ...102 Start up ...
Страница 108: ...108 Maintenance ...
Страница 140: ...140 Technical data ...
Страница 158: ...158 Mains chokes ...
Страница 164: ...164 EMC filters 7 Attach the terminal blocks to the filter 1 6 5 4 3 ...
Страница 166: ...166 EMC filters 6 Attach the terminal blocks to the filter 1 2 3 4 ...
Страница 168: ...168 EMC filters ...
Страница 182: ...Dimension drawings 182 Frame size R1 H1 H2 W D ...
Страница 183: ...Dimension drawings 183 Frame size R2 H2 H1 W D ...
Страница 184: ...Dimension drawings 184 Frame size R3 D W H1 H2 ...
Страница 185: ...Dimension drawings 185 Frame size R4 W H1 H2 D ...
Страница 187: ...187 Dimension drawings EMC filters type JFI x1 JFI A1 ...
Страница 188: ...Dimension drawings 188 JFI B1 ...
Страница 189: ...189 Dimension drawings EMC filters type JFI 0x ...
Страница 191: ...191 Dimension drawings Brake resistors type JBR xx ...
Страница 193: ...193 Dimension drawings ...
Страница 195: ...www abb com drives www abb com drivespartners 3AXD50000028613 Rev A EN 2016 04 11 Contact us ...