Fault tracing 433
80A0
AI supervision
Programmable fault:
An analog signal is outside
the limits specified for the
analog input.
Check signal level at the analog
input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter
group
Check the auxiliary code.
80B0
Signal supervision
(Editable message text)
Programmable fault:
Fault generated by a signal
supervision function.
Check the source of the fault
(parameter
).
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 2 function.
Check the source of the fault
(parameter
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 3 function.
Check the source of the fault
(parameter
9081
External fault 1
(Editable message text)
Programmable fault:
Fault in external device 1.
Check the external device.
Check setting of parameter
9082
External fault 2
(Editable message text)
Programmable fault:
Fault in external device 2.
Check the external device.
Check setting of parameter
9083
External fault 3
(Editable message text)
Programmable fault:
Fault in external device 3.
Check the external device.
Check setting of parameter
9084
External fault 4
(Editable message text)
Programmable fault:
Fault in external device 4.
Check the external device.
Check setting of parameter
9085
External fault 5
(Editable message text)
Programmable fault:
Fault in external device 5.
Check the external device.
Check setting of parameter
FA81
Safe torque off 1 loss
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Check safety circuit connections.
For more information, see
appropriate drive hardware manual
and description of parameter
(page
).
Check the auxiliary code, The code
contains location information,
especially with parallel-connected
inverter modules
FA82
Safe torque off 2 loss
Safe torque off function is
active, ie. STO circuit 2 is
broken.
Code
(hex)
Fault
Cause
What to do
Содержание ACS880 ESP
Страница 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Страница 4: ......
Страница 28: ...28 PCP ESP control start up ...
Страница 30: ...30 Using the control panel ...
Страница 94: ...94 Standard programposi features ...
Страница 100: ...100 Default control connections ...
Страница 360: ...360 Parameters ...
Страница 362: ...362 Additional parameter data Fieldbus addresses Refer to the User s Manual of the fieldbus adapter ...
Страница 436: ...436 Fault tracing ...
Страница 486: ...486 Control chain diagrams ...
Страница 492: ...492 Appendix ESP with step up transformer and sine filter ...
Страница 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...