430 Fault tracing
7358
Line side converter faulted
The supply unit has tripped
on a fault.
If using a control panel or the Drive
composer tool, connect to the
supply unit to read the fault code.
Refer to the firmware manual of the
supply unit for instructions related
to the code.
7380
Encoder internal
Internal fault.
Contact your local ABB
representative.
7381
Encoder 1
Programmable fault:
Encoder 1 feedback fault.
If fault appears during first start-up
before encoder feedback is used:
- Check cable between encoder
and encoder interface module
(FEN-xx) and order of connector
signal wires at both ends of cable.
If absolute encoder,
EnDat/Hiperface/SSI, with
incremental sin/cos pulses is used,
incorrect wiring can be located as
follows: Disable serial link (zero
position) by setting parameter
91.02 to 0 and test encoder
operation:
- If encoder fault is not activated,
check serial link data wiring. Note
that zero position is not taken into
account when serial link is
disabled.
- If encoder fault is activated, check
serial link and sin/cos signal wiring.
Note:
Because only zero position
is requested through serial link and
during, position is updated
according to sin/cos pulses.
- Check encoder parameter
settings.
If fault appears after encoder
feedback has already been used or
during drive:
- Check that encoder connection
wiring or encoder is not damaged.
- Check that encoder interface
module (FEN-xx) connection or
module is not damaged.
- Check earthings (when
disturbances are detected in
communication between encoder
interface module and encoder).
For more information on encoders,
see parameter groups
,
,
Check the event log for an auxiliary
code. See appropriate actions for
each code at
or
(page
).
7391
Encoder 2
Encoder 2 feedback fault.
Code
(hex)
Fault
Cause
What to do
Содержание ACS880 ESP
Страница 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Страница 4: ......
Страница 28: ...28 PCP ESP control start up ...
Страница 30: ...30 Using the control panel ...
Страница 94: ...94 Standard programposi features ...
Страница 100: ...100 Default control connections ...
Страница 360: ...360 Parameters ...
Страница 362: ...362 Additional parameter data Fieldbus addresses Refer to the User s Manual of the fieldbus adapter ...
Страница 436: ...436 Fault tracing ...
Страница 486: ...486 Control chain diagrams ...
Страница 492: ...492 Appendix ESP with step up transformer and sine filter ...
Страница 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...