Ambient conditions
Environmental limits for the converter are given below. The converter must be used in a
heated, indoor controlled environment.
Transportation
in protect-
ive package
Storage
in protective
package
Operation
installed for
stationary use
-
-
0 … 1000 m (0 … 3281 ft)
above sea level. Above
1000 m (3281 ft), see the
derating instructions.
Installation site altitude
-40 … +70 °C
(-40 … +158 °F)
-40 … +70 °C
(-40 … +158 °F)
-30 … +50 °C
(-22 … +122 °F) (with
heating procedure below
+5 °C before start-up)
Freezing of coolant is not
allowed. Above +50 °C
(+122 °F), see the derating
instructions.
Air temperature
0 … 95%
0 … 95%
0 … 95%
Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
No conductive dust allowed.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
Boards with coating:
Chemical gases: Class
2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class
1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class
3C2
Solid particles: Class 3S2
60 … 106 kPa
0.6 … 1.05 atmospheres
70 … 106 kPa
0.7 … 1.05 atmospheres
70 … 106 kPa
0.7 … 1.05 atmospheres
Atmospheric pressure
Max. 3.5 mm (0.14 in)
(2 … 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 … 200 Hz) sinusoidal
10 … 58 Hz, max.
0.075 mm displacement
amplitude
58…150 Hz 10 m/s
2
10 … 58 Hz, max.
0.075 mm displacement
amplitude
58…150 Hz 10 m/s
2
Vibration
(IEC 60068-2-6)
Max. 100 m/s
2
(330 ft/s
2
),
11 ms
Max. 100 m/s
2
(330 ft/s
2
),
11 ms
Not allowed
Shock
(IEC 60068-2-27)
100 mm (4 in)
100 mm (4 in)
Not allowed
Free fall
Technical data 97
Содержание ACS880-87LC-3200A
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS880 87LC 3200A 3200A 7 wind turbine converters Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Страница 48: ...48 ...
Страница 68: ...68 ...
Страница 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Страница 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Страница 108: ...108 ...
Страница 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Страница 116: ...116 Dimension drawings ...
Страница 117: ...Dimension drawings 117 ...
Страница 118: ...118 Dimension drawings ...
Страница 130: ...130 ...