Work on the liquid cooling system
These instructions are intended for all who are responsible for installation and maintenance
work of the liquid cooling system of the converter.
WARNING!
Obey these instructions. If you ignore them, injury or damage to the equipment
can occur.
• Use protective eyewear when working with the liquid cooling system.
• Beware of hot liquid. Do not work on the liquid cooling system until the pressure
is lowered down by stopping the pumps. High-pressure hot coolant (600 kPa,
over 50 °C/122 °F) is present in the internal cooling circuit when the converter
is in operation.
• Before power switch-on, make sure that the internal cooling circuit is filled up
with coolant. Running the external cooling pump dry will damage it. Also the
converter will not cool down.
• Avoid skin contact with coolant, especially antifreeze. Do not syphon them by
mouth. If such substance is swallowed or gets into the eyes, seek medical
advice.
• To avoid breaking the coolant pipes, do not overtighten the nuts of the unions.
• Blue connectors: Leave 2…3 millimeters (0.08 … 0.12 inches) of thread
visible.
2...3 mm
• Black connectors: Tightening torque is 10 N·m (7.4 lbf·ft) in room temperature
(20 °C/68 °F).
• If the ambient temperature is below +5 °C (41 °F), add antifreeze and corrosion
inhibitors to the cooling liquid.
• Drain the system before storing in temperatures below 0 °C (32 °F). Freezing
of the liquid cooling system is not allowed. Operation at liquid temperatures
below zero is not permitted, not even with antifreeze.
22 Safety instructions
3
Содержание ACS880-87LC-3200A
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS880 87LC 3200A 3200A 7 wind turbine converters Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Страница 48: ...48 ...
Страница 68: ...68 ...
Страница 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Страница 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Страница 108: ...108 ...
Страница 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Страница 116: ...116 Dimension drawings ...
Страница 117: ...Dimension drawings 117 ...
Страница 118: ...118 Dimension drawings ...
Страница 130: ...130 ...