Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
IEC 60721-3-2:1997
IEC 60721-3-1:1997
IEC/EN 60721-3-3:2002:
Classification of environ-
mental conditions - Part 3-
3: Classification of groups
of environmental paramet-
ers and their severities -
Stationary use of weather
protected locations
Contamination
Chemical gases: Class
2C2
Solid particles: Class 2S2
Chemical gases: Class
1C2
Solid particles: Class 1S3
(packing must support this,
otherwise 1S2)
Chemical gases: Class
3C2
Solid particles: Class 3S2.
No conductive dust al-
lowed.
2
Pollution degree
IEC/EN 60721-3-2:1997
IEC/EN 60721-3-1:1997
IEC/EN 60721-3-3:2002
Vibration
2…9 Hz: max. 3.5 mm
amplitude
10…57 Hz: max. 0.075 mm
amplitude
10…57 Hz: max. 0.075 mm
amplitude
IEC/EN 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008 Envir-
onmental testing Part 2:
Tests –Test Fc: Vibration
(sinusoidal)
9…200 Hz: 10 m/s
2
(32.8 ft/s
2
)
57…150 Hz: 1
g
57…150 Hz: 1
g
Units with marine construc-
tion (C121): Max.
1 mm (0.04 in)
(5 … 13.2 Hz), max. 0.7
g
(13.2 … 100 Hz) sinusoidal
With packing max.
100 m/s
2
(328 ft/s
2
) 11 ms
With packing max.
100 m/s
2
(328 ft/s
2
) 11 ms
Not allowed
Shock
IEC 60068-2-27:2008, EN
60068-2-27:2009
Environmental testing -
Part 2-27: Tests - Test Ea
and guidance: Shock
Materials
See
ACS880 cabinet-installed drives recycling instructions and environmental information
(3AXD50000153909 [English]).
For material and recycling information of the DC breaker switch, contact the manufacturer
Astrol Electronic AG.
Color
RAL 7035 and RAL 9017.
60 Technical data
Содержание ACS880-7407LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 7407LC semiconductor switch units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 22: ...22 ...
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 36: ...36 ...
Страница 54: ...54 ...
Страница 56: ...56 ...