Use as motor cabling
Use as input power cabling
Cable type
No
Yes
PE
WARNING!
If you use unshielded
single-core cables in an IT
network, make sure that the
non-conductive outer
sheath (jacket) of the cables
have good contact with a
properly grounded conduct-
ive surface. For example,
install the cables on a prop-
erly grounded cable tray.
Otherwise voltage may be-
come present on the non-
conductive outer sheath of
the cables, and there is
even a risk of an electric
shock.
A single-core cable system: three
phase conductors and PE conductor
on cable tray
L1
L3
L2
L2
L1
L3
L3
L2
L1
Preferable cable arrangement to
avoid voltage or current unbalance
between the phases
Not allowed power cable types
Use as motor cabling
Use as input power cabling
Cable type
No
No
PE
Symmetrical shielded cable with in-
dividual shields for each phase
conductor
■
Power cable shield
If the cable shield is used as the sole protective earth (PE) conductor, make sure that its
conductivity agrees with the PE conductor requirements.
To effectively suppress radiated and conducted radio-frequency emissions, the cable shield
conductivity must be at least 1/10 of the phase conductor conductivity. The requirements
are easily met with a copper or aluminum shield. The minimum requirement of the motor
cable shield of the drive is shown below. It consists of a concentric layer of copper wires
with an open helix of copper tape or copper wire. The better and tighter the shield, the lower
the emission level and bearing currents.
Guidelines for planning the electrical installation 65
Содержание ACS880-37LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 78: ...78 ...
Страница 116: ...116 ...
Страница 134: ...5 Set the real time clock 134 Maintenance ...
Страница 144: ...144 ...
Страница 167: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 167 ...
Страница 169: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 169 ...
Страница 170: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 170 Dimensions ...
Страница 171: ...Cabinet height and depth Marine construction option C121 IP42 side view Non marine IP42 side view Dimensions 171 ...
Страница 172: ...Location and size of input terminals Contact ABB for details 172 Dimensions ...
Страница 174: ...Inverter module cubicle with two R8i modules bottom cable exit 174 Dimensions ...
Страница 175: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 175 ...
Страница 176: ...Brake chopper cubicle D150 176 Dimensions ...
Страница 177: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit Dimensions 177 ...
Страница 178: ...Cubicle width 300 mm top cable exit 178 Dimensions ...
Страница 179: ...Cubicle width 400 mm bottom cable exit Dimensions 179 ...
Страница 180: ...Cubicle width 400 mm top cable exit 180 Dimensions ...
Страница 181: ...Cubicle width 600 mm bottom cable exit Dimensions 181 ...
Страница 182: ...Cubicle width 600 mm top cable exit 182 Dimensions ...
Страница 198: ...198 ...
Страница 200: ...200 ...