External control unit 111
DI6 (XDI:6) as PTC sensor input
One PTC sensor can be connected to this input for motor temperature measurement as
follows. The sum of the sensor resistances must not exceed the threshold resistance of
the digital input at the motor normal operating temperature. Do not connect both ends of
the cable shield directly to ground. If a capacitor cannot be used at one end, leave that end
of the shield unconnected. See the firmware manual for the parameter settings.
DIIL input (XD24:1)
The DIIL input can used for the connection of safety circuits. By default, the input is
parametrized to stop the drive when the input signal is lost.
Drive-to-drive link (XD2D)
The drive-to-drive link is a daisy-chained RS-485 transmission line that can be used for
•
basic master/follower communication with one master drive and multiple followers
•
fieldbus control through the embedded fieldbus interface (EFB), and
•
drive-to-drive (D2D) communication implemented by application programming.
See the firmware manual of the drive for the related parameter settings.
Set termination activation jumper J3 next to this terminal block to the ON position on the
drives at the ends of the drive-to-drive link. On intermediate drives, set the jumper to the
OFF position.
Use shielded twisted-pair cable with a twisted pair for data and a wire or another pair for
signal ground (nominal impedance 100 to 165 ohm, for example Belden 9842) for the
wiring. For best immunity, ABB recommends high quality cable. Keep the cable as short as
possible. Avoid unnecessary loops and running the cable near power cables (such as
motor cables).
WARNING!
As the inputs pictured above are not insulated according to
IEC 60664, the connection of the motor temperature sensor requires double or
reinforced insulation between motor live parts and the sensor. If the assembly
does not fulfill the requirement, the I/O board terminals must be protected against contact
and must not be connected to other equipment or the temperature sensor must be
isolated from the I/O terminals.
T
PTC
DI6
+24VD
“0” > 4 kohm
“1” < 1.5 kohm
I
max
= 5 mA
Содержание ACS880-34
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 Safety instructions ...
Страница 28: ...28 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 118: ...118 External control unit ...
Страница 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Страница 152: ...152 Installation checklist ...
Страница 156: ...156 Start up ...
Страница 158: ...158 Fault tracing ...
Страница 174: ...174 Maintenance ...
Страница 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Страница 204: ...204 Technical data ...
Страница 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Страница 207: ...Dimension drawings 207 Location of power cable connection terminals with options H370 H356 3AXD50000038012 ...
Страница 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Страница 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Страница 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Страница 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Страница 238: ...238 Resistor braking ...
Страница 242: ...242 du dt and sine filters ...
Страница 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...