Electrical power network specification
690 V units: 525…690 V AC 3-phase ± 10% (525…600 V AC ± 10% in UL/CSA
installations, or corner-grounded TN systems). This is indicated in the type desig-
nation label as typical input voltage levels (3~ 525/600/690 V AC).
Voltage (
U
1
)
TN (grounded) and IT (ungrounded) systems
Network type
50/60 Hz, variation ± 5% of nominal frequency
Frequency
Max. ± 3% of nominal phase-to-phase input voltage
Imbalance
Supply units with main circuit breaker (F255) and without grounding/earthing
switch (without F259):
Short-circuit withstand
strength (IEC/EN 61439-1)
Rated peak withstand current (
I
pk
): 143 kA
Rated short-time withstand current (
I
cw
): 65 kA/1 s
All other configurations:
Rated peak withstand current (
I
pk
): 105 kA
Rated short-time withstand current (
I
cw
): 50 kA/1 s
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with class T fuses.
Short-circuit current protec-
tion (UL 508A, CSA C22.2
No. 14-13)
Connection: Dy 11 d0 or Dyn 11 d0
Transformer specification
for 12-pulse supply
(IEC 60076-1:2011)
Phase shift between secondaries: 30° electrical
Voltage difference between secondaries: < 0.5%
Short-circuit impedance of secondaries: > 5%
Short-circuit impedance difference between secondaries: ≤ 10% of the percentage
impedance
To avoid a potentially destructive DC voltage level in an earth fault situation,
grounding of the secondaries is not allowed. Static shielding is recommended.
Control unit (board) connection data
See
.
Auxiliary circuit current consumption
Auxiliary circuit current consumption varies depending on the actual drive configuration and
options. Contact ABB for the delivery-specific value.
Efficiency
98.2…98.8% at nominal power level depending on drive type
Efficiency
Protection classes
IP42 (standard), IP54 (B055)
Degrees of protection
(IEC/EN 60529)
UL Type 1 (standard), UL Type 12 (B055). For indoor use only.
Enclosure types (UL50)
III, except for auxiliary power connections (fan, control, heating, lighting, cooling
unit pump etc) which are category II.
Overvoltage category
(IEC/EN 60664-1)
I
Protective class
(IEC/EN 61800-5-1)
Technical data 101
Содержание ACS880-307LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 307LC diode supply units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 34: ...34 ...
Страница 40: ...11 Reinstall the shrouding removed earlier 12 Close the door 3 PE PE 40 Electrical installation ...
Страница 41: ...10 9 7 6 8 Electrical installation 41 11 ...
Страница 73: ...11 12 12 6 10 Maintenance 73 ...
Страница 78: ...78 ...
Страница 88: ...88 ...
Страница 96: ... 400 mm wide input cubicle 96 Technical data ...
Страница 97: ... 600 mm wide incoming cubicle or input cubicle Technical data 97 ...