Main circuit diagram
The figure shows a simplified main circuit diagram of the rectifier bridge.
16 Operation principle and hardware description
Main circuit diagram
The figure shows a simplified main circuit diagram of the rectifier bridge.
Implementing DC voltage measurement
The control program needs a measured voltage value:
•
for the control of the charging circuit at the power up
•
for overvoltage and undervoltage monitoring and protection.
The supply unit does not have the DC voltage measurement as standard. The cabinet
installer must implement it separately. The cabinet installer can, for example:
1. connect the DC voltage measurement of the inverter unit to the supply unit via a fiber
optic link. For more information, see
Setting the parameters
on page
84
,
Example
, and the relevant firmware manuals.
2. connect the DC voltage measurement of the inverter unit to the supply unit via the
analog output of the inverter unit and analogue input AI2 or AI1 of the supply unit. For
more information, see
Setting the parameters
on page
84
,
Example circuit diagrams
on page
169
, and the relevant firmware manuals.
3. use a separate voltage measurement device (transducer), and connect it between the
drive DC link and analogue input AI2 or AI1 of the supply unit.
You can use alternatives 1, 2, or 3 for a single drive, in other words, for a drive that consist
of one supply unit and one inverter unit. For multidrives (one supply unit feeds several
inverters), use alternative 3.
Charging
A charging circuit powers up the DC link capacitors of the drive system smoothly.
Discharged capacitors cannot be directly connected to the full supply voltage. The
charging current must be limited until the capacitors are charged and ready for normal use.
If the diode supply unit is equipped with a charging circuit, the DC voltage level must be
signaled to the control unit either through analog input AI2 (AI1) or fiber optic connection
1. AC fuses
2. Diodes
+
-
U
c
+
-
U
c
2
2
1
AC fuses
1
Diodes
2
■
Implementing DC voltage measurement
The control program needs a measured voltage value:
•
for the control of the charging circuit at the power up
•
for overvoltage and undervoltage monitoring and protection.
The supply unit does not have DC voltage measurement as standard. The cabinet
installer must implement it separately. The cabinet installer can, for example:
1.
connect the DC voltage measurement of the inverter unit to the supply unit via a
fiber optic link between DDCS communication modules. For more information,
see
,
Example circuit diagrams (page 153)
and the relevant
firmware manuals.
2.
connect the DC voltage measurement of the inverter unit to the supply unit via
the analog output of the inverter unit and analogue input AI2 or AI1 of the supply
unit. For more information, see
and the relevant firmware manuals.
3.
use a separate voltage measurement device (transducer), and connect it between
the drive DC link and analogue input AI2 or AI1 of the supply unit.
You can use alternatives 1, 2, or 3 for a single drive, in other words, for a drive that
consist of one supply unit and one inverter unit. For multidrives (one supply unit feeds
several inverters), use alternative 3.
■
Charging
A charging circuit powers up the DC link capacitors of the drive system smoothly.
Discharged capacitors cannot be directly connected to the full supply voltage. The
charging current must be limited until the capacitors are charged and ready for normal
use.
16 Operation principle and hardware description
Содержание ACS880-304LC Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 45: ... Kits for D8D supply modules in 400 mm Rittal VX25 or generic enclosure Cabinet construction 45 10 ...
Страница 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Страница 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Страница 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Страница 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Страница 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Страница 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Страница 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Страница 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Страница 54: ...54 ...
Страница 74: ...74 ...
Страница 87: ...5 Maintenance 87 ...
Страница 88: ...6 7 8 9 9 88 Maintenance ...
Страница 92: ...92 ...
Страница 108: ...108 ...
Страница 118: ...118 ...
Страница 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Страница 142: ...ZCU 14 control unit 142 Dimension drawings ...
Страница 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Страница 144: ...CIO 01 module 144 Dimension drawings ...
Страница 152: ...152 ...