Tasks
Powering up the auxiliary circuit of the supply unit
Make sure that it is safe to connect voltage. Make sure that:
•nobody is working on the unit or circuits that are wired from outside into the cabinets
•covers of the motor terminal boxes are on.
Supply unit with the voltage meters on door ([F5], G334): Close the circuit breaker for the
meters.
Close the circuit breakers supplying the auxiliary circuits [F22,..., F26].
Close the cabinet doors.
Close the disconnector and breaker of the supply transformer. The drive input power terminals are
energized.
Switch the auxiliary voltage switch [Q21] on. The drive auxiliary circuit is energized.
Supply unit with the grounding switch ([Q9], F259): Open the grounding switch.
WARNING!
Do not use excessive force. If the unit is equipped with a grounding switch [Q9], electromag-
netic interlocking is also used. You cannot switch the main switch-disconnector [Q1] on before
its lock release relay [K1] is energized, that is:
•the main input terminals [L1, L2 and L3] are powered, and
•auxiliary voltage switch [Q21] is switched on, and
•circuit breakers [F22 and F23] in between the relay [K1] and auxiliary voltage switch [Q21]
are switched on.
Setting up the supply unit parameters
Check the correct voltage range, parameter
195.01 Supply voltage
.
If your supply unit consists of more than one module, parameters
195.30 Parallel type filter
and
195.31
Parallel connection rating id
need to be set. First, select the correct voltage range with parameter
195.30 Parallel type filter
. Then, select the correct supply unit type with parameter
195.31 Parallel
connection rating id
.
See also
ACS880 IGBT supply control program firmware manual
(3AUA0000131562 [English]).
If you need more information on the use of the control panel, see
ACS-AP-x assistant control panels
user's manual
(3AUA0000085685 [English]).
Switch the control panel to the remote mode (Loc/Rem key) to enable control of the supply unit with
the operating switch [S21].
Drives with a fieldbus adapter (optional): Set the fieldbus parameters. Activate the fieldbus adapter
module in the control program. See the user’s manual of the fieldbus adapter module, and
ACS880
IGBT supply control program firmware manual
(3AUA0000131562 [English]).
Powering up the main circuit of the drive
Close the main disconnecting device:
Supply unit with main switch-disconnector ([Q1], F253): Close the main switch-disconnector
[Q1].
Supply unit with main breaker ([Q1], F255): Rack in the main breaker [Q1].
Note:
The grounding switch ([Q9], F259) must be switched off.
WARNING!
Do not use excessive force. There is electromagnetic interlocking in use. See section
magnetic interlocking (page 70)
.
Switch the charging circuit switch fuse [Q3] on.
Start-up 69
12
Содержание ACS880-207
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 207 IGBT supply units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 53: ... 3 3 Electrical installation 53 11 ...
Страница 54: ...3 54 Electrical installation ...
Страница 81: ...4 5 6 7 8 6 10 10 Maintenance 81 ...
Страница 94: ...5 6 10 3 4 7 9 8 94 Maintenance ...
Страница 99: ... Maintenance 99 ...
Страница 100: ... 100 Maintenance ...
Страница 103: ...5 6 3 4 8 9 7 Maintenance 103 ...
Страница 107: ...5 6 3 4 7 Maintenance 107 ...