Guidelines for planning the electrical installation 71
5
Guidelines for planning the
electrical installation
Contents of this chapter
This chapter contains instructions for planning the electrical installation of the drive. Some
instructions are mandatory to follow in every installation, others provide useful information
that only concerns certain applications.
Limitation of liability
The installation must always be designed and made according to applicable local laws and
regulations. ABB does not assume any liability whatsoever for any installation which
breaches the local laws and/or other regulations. Furthermore, if the recommendations
given by ABB are not followed, the drive may experience problems that the warranty does
not cover.
Selecting the supply disconnecting device
The drive is equipped with a main disconnecting device. Depending on the size of the
drive, the disconnecting device is a switch-disconnector or an air circuit breaker. The
disconnecting device can be locked to the open position for installation and maintenance
work.
Selecting the main contactor
Depending on type, the drive is equipped with either a main contactor or an air circuit
breaker. See
Overview circuit diagram of the drive
).
Содержание ACS880-17
Страница 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 16: ...16 ...
Страница 30: ...30 Introduction to the manual ...
Страница 61: ...Mechanical installation 61 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 70: ...70 Mechanical installation ...
Страница 105: ...Electrical installation 105 4 5 3 6 7 ...
Страница 107: ...Electrical installation 107 5 6 4 3 ...
Страница 108: ...108 Electrical installation 7 8 8 ...
Страница 109: ...Electrical installation 109 9 10 ...
Страница 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Страница 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Страница 134: ...134 Control units of the drive ...
Страница 140: ...140 Start up ...
Страница 142: ...142 Fault tracing ...
Страница 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Страница 162: ...162 Maintenance 5 6 3 4 7 ...
Страница 163: ...Maintenance 163 6 8 7 11 10 9 ...
Страница 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Страница 185: ...Technical data 185 Declaration of Conformity ...
Страница 186: ...186 Technical data ...
Страница 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Страница 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Страница 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Страница 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Страница 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Страница 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Страница 202: ...202 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 1 2 ...
Страница 203: ...Dimensions 203 Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 2 2 ...
Страница 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Страница 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Страница 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Страница 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Страница 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Страница 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Страница 213: ...Dimensions 213 Units with main breaker 600 mm bottom cable entry Units with main breaker 600 mm top cable entry ...
Страница 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Страница 219: ...Dimensions 219 Cubicle width 300 mm double busbar version bottom cable exit Cubicle width 300 mm top cable exit ...
Страница 220: ...220 Dimensions Cubicle width 300 mm double busbar version top cable exit Cubicle width 400 mm bottom cable exit ...
Страница 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Страница 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Страница 234: ...234 The Safe torque off function ...
Страница 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...