Safety instructions 21
Electrical safety in installation, start-up and maintenance
Precautions before electrical work
These warnings are for all personnel who do work on the drive, motor cable or motor.
WARNING!
Obey these
instructions. If you ignore them, injury or death, or
damage to the equipment can occur. If you are not a qualified electrician, do not
do installation or maintenance work. Go through these steps before you begin any
installation or maintenance work.
1. Clearly identify the work location.
2. Disconnect all possible voltage sources.
•
Open the main switch-disconnector [Q1.1] or breaker [Q1] of the drive.
•
Open the disconnector of the supply transformer as the main switch-disconnector
or breaker of the drive does not remove the voltage from the input busbars of the
drive.
•
Make sure that reconnection is not possible. Lock the disconnectors to open
position and attach a warning notice to them.
•
Disconnect any external power sources from the control circuits before you do
work on the control cables.
•
After you disconnect the drive, always wait for 5 minutes to let the intermediate
circuit capacitors discharge before you continue.
3. Protect any other energized parts in the work location against contact.
4. Take special precautions when close to bare conductors.
5. Measure that the installation is de-energized.
•
Use a multimeter with an impedance of at least 1 Mohm.
•
Make sure that the voltage between the drive input power terminals (L1, L2, L3)
and the grounding (PE) busbar is close to 0 V.
•
Make sure that the voltage between the drive DC busbars (+ and -) and the
grounding (PE) busbar is close to 0 V.
6. Install temporary grounding as required by the local regulations. Close the grounding
switch (F259, Q9) if present.
7. Ask the person in control of the electrical installation work for a permit to work.
Содержание ACS880-17
Страница 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 16: ...16 ...
Страница 30: ...30 Introduction to the manual ...
Страница 61: ...Mechanical installation 61 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 70: ...70 Mechanical installation ...
Страница 105: ...Electrical installation 105 4 5 3 6 7 ...
Страница 107: ...Electrical installation 107 5 6 4 3 ...
Страница 108: ...108 Electrical installation 7 8 8 ...
Страница 109: ...Electrical installation 109 9 10 ...
Страница 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Страница 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Страница 134: ...134 Control units of the drive ...
Страница 140: ...140 Start up ...
Страница 142: ...142 Fault tracing ...
Страница 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Страница 162: ...162 Maintenance 5 6 3 4 7 ...
Страница 163: ...Maintenance 163 6 8 7 11 10 9 ...
Страница 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Страница 185: ...Technical data 185 Declaration of Conformity ...
Страница 186: ...186 Technical data ...
Страница 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Страница 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Страница 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Страница 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Страница 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Страница 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Страница 202: ...202 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 1 2 ...
Страница 203: ...Dimensions 203 Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 2 2 ...
Страница 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Страница 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Страница 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Страница 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Страница 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Страница 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Страница 213: ...Dimensions 213 Units with main breaker 600 mm bottom cable entry Units with main breaker 600 mm top cable entry ...
Страница 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Страница 219: ...Dimensions 219 Cubicle width 300 mm double busbar version bottom cable exit Cubicle width 300 mm top cable exit ...
Страница 220: ...220 Dimensions Cubicle width 300 mm double busbar version top cable exit Cubicle width 400 mm bottom cable exit ...
Страница 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Страница 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Страница 234: ...234 The Safe torque off function ...
Страница 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...