Note
Max. torque
Size
Strength class 8.8
9 N·m (6.6 lbf·ft)
M8
Strength class 8.8
18 N·m (13.3 lbf·ft)
M10
Strength class 8.8
31 N·m (23 lbf·ft)
M12
■
Cable lugs
Note
Max. torque
Size
Strength class 8.8
15 N·m (11 lbf·ft)
M8
Strength class 8.8
32 N·m (23.5 lbf·ft)
M10
Strength class 8.8
50 N·m (37 lbf·ft)
M12
Input power (DC bus) connection
ACS880-1607LC-xxxxx-7 = 742 … 976 V DC. This is indicated in the type
designation label as typical input range 50…742 / 849 / 976 V DC.
Voltage (U
1
)
TN (grounded) and IT (ungrounded) systems, corner-grounded systems up
to 600 V AC
Drive AC supply network type
M12, maximum intrusion into module 20 mm (0.8"). Torque: 70 N·m (52 lbf·ft).
Input terminals
Output power (energy storage) connection
ACS880-1607LC-xxxxx-7 = Maximum output voltage 150 V…95% of
U
DC
(Drive DC voltage in the DC bus). This is indicated in the type designation
label as typical output voltage range 50…688 / 764 / 878 V DC.
Recommended output voltage 150 V…80% of
U
DC
.
Voltage (U
2
)
See section
.
Current
Control accuracy – Current and voltage control
performance data
Step response time < 10 ms for a reference step 0% to 50% of the drive
nominal current
Current control dynamic re-
sponse
Current error < 1% of the drive nominal current rating
For the DC current ripple, see
.
Current control accuracy
(static)
Voltage error < 1% of the drive nominal voltage (converter with the optional
BAMU voltage/current measurement unit, G442
Note:
If the converter does not include the BAMU voltage/current measurement
unit, the voltage measurement accuracy depends on the customer's measure-
ment device.
ES voltage control accuracy
(static)
Coolant connections
Tube fitting, quick coupler for 16/13 mm polyamide (PA) pipe.
96 Technical data
Содержание ACS880-1607LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 1607LC DC DC converter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 32: ...32 ...
Страница 38: ...38 ...
Страница 60: ...60 ...
Страница 80: ...80 ...
Страница 90: ...90 ...
Страница 102: ...Unit with 1 R8i converter module 102 Dimension drawings ...
Страница 103: ...Dimension drawings 103 ...
Страница 104: ...Location and size of energy storage connection terminals 104 Dimension drawings ...