Connecting motor temperature sensor to the drive via an option module
This table shows:
• option module types that you can use for the motor temperature sensor connection
• insulation or isolation level that each option module forms between its temperature
sensor connector and other connectors
• temperature sensor types that you can connect to each option module
• temperature sensor insulation requirement in order to form, together with the
insulation of the option module, a reinforced insulation between the motor live parts
and the drive control unit.
Temperature sensor insula-
tion requirement
Temperature
sensor type
Option module
Pt100,
Pt1000
KTY
PTC
Insulation/Isolation
Type
Reinforced insulation
x
x
-
Galvanic isolation between
sensor connector and other
connectors (including drive
control unit connector)
FIO-11
Reinforced insulation
-
x
x
Galvanic isolation between
sensor connector and other
connectors (including drive
control unit connector)
FEN-xx
Basic insulation. Connectors of
option module other than
sensor connector must be left
unconnected.
x
x
x
Basic insulation between
sensor connector and drive
control unit connector. No insu-
lation between sensor connect-
or and other I/O connectors.
FAIO-
01
No special requirement
-
-
x
Reinforced insulation between
sensor connector and other
connectors (including drive
control unit connector).
FPTC-
xx
1)
1) Suitable for use in safety functions (SIL2 / PL c rated).
Protecting the drive against ground faults
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable. This function is not a personnel
safety or a fire protection feature. See the firmware manual for more information.
■
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
76 Guidelines for planning the electrical installation
Содержание ACS880-11
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 52: ...52 ...
Страница 82: ...82 ...
Страница 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Страница 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Страница 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Страница 112: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 112 Electrical installation IEC ...
Страница 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Страница 120: ...R3 7 7 8 8 L1 L2 L3 T1 U T2 V T3 W PE Ground 1 7 N m 1 2 lbf ft 120 Electrical installation North America NEC ...
Страница 142: ...142 ...
Страница 154: ... Fan arrow must point up 154 Maintenance ...
Страница 160: ...160 ...
Страница 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Страница 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Страница 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Страница 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Страница 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Страница 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Страница 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Страница 208: ...208 ...
Страница 225: ... Declarations of conformity The Safe torque off function 225 ...