The Safe torque off function
Contents of this chapter
This chapter describes the Safe torque off (STO) function of the inverter and gives instructions
for its use.
Description
WARNING!
In case of parallel-connected drives or dual-winding motors, the STO must be
activated on each drive to remove the torque from the motor.
The Safe torque off function can be used, for example, as the final actuator device of safety
circuits that stop the inverter in case of danger (such as an emergency stop circuit). Another
typical application is a prevention of unexpected start-up function that enables short-time
maintenance operations like cleaning or work on non-electrical parts of the machinery without
switching off the power supply to the inverter.
When activated, the Safe torque off function disables the control voltage of the power
semiconductors of the inverter output stage (A, see the diagrams below), thus preventing
the inverter from generating the torque required to rotate the motor. If the motor is running
when Safe torque off is activated, it coasts to a stop.
The Safe torque off function has a redundant architecture, that is, both channels must be
used in the safety function implementation. The safety data given in this manual is calculated
for redundant use, and does not apply if both channels are not used.
The Safe torque off function complies with these standards:
11
The Safe torque off function 183
Содержание ACS880-107
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 107 inverter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 64: ...2 4 5 6 7 8 11 10 3 a b a b b 1 5 a 64 Electrical installation ...
Страница 69: ...Electrical installation 109 5 6 4 3 Electrical installation 69 11 ...
Страница 70: ...7 a b d c 110 Electrical installation 7 8 8 8 9 9 70 Electrical installation ...
Страница 75: ...2 11 b PE 10 7 5 6 8 a 360 grounding detail Electrical installation 75 11 ...
Страница 89: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 89 11 ...
Страница 90: ...90 ...
Страница 96: ...96 ...
Страница 110: ...4 5 6 7 8 6 10 10 110 Maintenance ...
Страница 118: ...2 3 7 9 a a c c c 6 8 b b d d 11 e e 118 Maintenance ...
Страница 121: ...7 a b d c 110 Electrical installation 7 8 8 8 9 9 Maintenance 121 ...
Страница 130: ...130 ...
Страница 154: ...154 ...
Страница 155: ...Circuit diagrams Refer to the circuit diagrams delivered with the unit 9 Circuit diagrams 155 ...
Страница 156: ...156 ...
Страница 159: ... Dimension drawing 400 mm wide cubicle R1i R4i 400 mm R6i R7i Dimensions and weights 159 ...
Страница 161: ... Dimension drawing R8i without C128 or H353 bottom cable exit Dimensions and weights 161 ...
Страница 162: ... Dimension drawing R8i without C128 or H353 top cable exit 162 Dimensions and weights ...
Страница 163: ... Dimension drawing 2 R8i without C128 or H353 bottom cable exit Dimensions and weights 163 ...
Страница 164: ... Dimension drawing 2 R8i without C128 or H353 top cable exit 164 Dimensions and weights ...
Страница 165: ... Dimension drawing 3 R8i without C128 or H353 bottom cable exit Dimensions and weights 165 ...
Страница 166: ... Dimension drawing 3 R8i without C128 or H353 top cable exit 166 Dimensions and weights ...
Страница 167: ... Dimension drawing drive control unit DCU 300 mm Dimensions and weights 167 ...
Страница 169: ...Inverter module cubicle with one R8i module top cable exit Dimensions and weights 169 ...
Страница 177: ...Cubicle width 300 mm top cable exit 246 Dimensions Cubicle width 300 mm top cable exit Dimensions and weights 177 ...
Страница 179: ...Cubicle width 400 mm top cable exit Cubicle width 400 mm top cable exit Dimensions and weights 179 ...
Страница 181: ...Cubicle width 600 mm top cable exit Cubicle width 600 mm top cable exit Dimensions and weights 181 ...
Страница 182: ...182 ...
Страница 200: ...200 ...