1
3
4
5
2
Insulation jacket
1
Helix of copper tape or copper wire
2
Copper wire shield
3
Inner insulation
4
Cable core
5
Selecting the control cables
■
Shielding
Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. This type of cable is
recommended for the pulse encoder signals also. Use one individually shielded pair for
each signal. Do not use common return for different analog signals.
A double-shielded cable (a) is the best alternative for low-voltage digital signals, but
single-shielded (b) twisted pair cable is also acceptable.
a
b
■
Signals in separate cables
Run analog and digital signals in separate, shielded cables. Do not mix 24 V DC and
115/230 V AC signals in the same cable.
■
Signals that can be run in the same cable
If their voltage does not exceed 48 V, relay-controlled signals can be run in the same cables
as digital input signals. The relay-controlled signals should be run as twisted pairs.
■
Relay cable
The cable type with braided metallic shield (for example ÖLFLEX by LAPPKABEL, Germany)
has been tested and approved by ABB.
■
Control panel to drive cable
Use EIA-485 with male RJ-45 connector, cable type Cat 5e or better. The maximum permitted
length of the cable is 100 m (328 ft).
74 Guidelines for planning the electrical installation
Содержание ACS880-07LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 07LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...16 Resistor braking Further information 12 Table of contents ...
Страница 22: ...22 ...
Страница 63: ...Mechanical installation 63 10 ...
Страница 64: ...64 ...
Страница 91: ...a b c 4 a 8 b 16 18 PE PE 10 13 12 Electrical installation 91 11 ...
Страница 97: ...11 Reinstall the shrouding removed earlier 12 Close the cubicle door Electrical installation 97 11 ...
Страница 100: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 100 Electrical installation ...
Страница 104: ...104 ...
Страница 118: ...118 ...
Страница 124: ...124 ...
Страница 138: ...8 9 138 Maintenance ...
Страница 139: ...11 12 12 6 10 Maintenance 139 ...
Страница 150: ...150 ...
Страница 160: ...160 ...
Страница 183: ...Technical data 183 ...
Страница 184: ...184 Technical data ...
Страница 189: ... Dimension drawing examples ACS880 07LC 0850A 7 Dimensions 189 ...
Страница 190: ...ACS880 07LC 1660A 7 6 pulse 190 Dimensions ...
Страница 191: ...ACS880 07LC 1660A 7 A004 12 pulse Dimensions 191 ...
Страница 192: ...ACS880 07LC 3260A 7 192 Dimensions ...
Страница 193: ...Cabinet height and depth Marine construction option C121 IP42 side view Non marine IP42 side view Dimensions 193 ...
Страница 194: ...Location and size of input terminals 600 mm with main breaker single busbar bottom cable entry 194 Dimensions ...
Страница 195: ... 600 mm with main breaker double busbar bottom cable entry Dimensions 195 ...
Страница 197: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 197 ...
Страница 198: ...Inverter module cubicle with three R8i modules bottom cable exit 198 Dimensions ...
Страница 199: ...Brake chopper cubicle Dimensions 199 ...
Страница 200: ...200 ...
Страница 216: ... Declaration of conformity 216 The Safe torque off function ...
Страница 217: ...The Safe torque off function 217 ...
Страница 218: ...218 ...
Страница 220: ...220 ...